Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM01872

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2008 MECHANICAL - ABOVE CEILING Approved
03/14/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 5B PATIENT ROOMS.
NEED TO SEE FIRE DAMPERS & ELEVATOR LOBBY.
03/07/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES AREA 4B
FINISH ANGLE AROUND FIRE DAMPER IN EQUIPMENT ROOM
AND PROVIDE AN ACCESS DOOR
03/04/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 4B
STILL NEED TO SEE FIRE & SMOKE DAMPERS
02/28/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SHEETROCK MISSING AT 1HR WALLS & FRAMING ALSO MISSING
LABEL FIRE & SMOKE DAMPER ACCESS DOORS
OK CEILING TILES PENDING OTHER INSPECTIONS!
02/13/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
TOILET ROOM 1-L14 PROVIDE ACCESS TO VAV AREA 1B
CLEAN PAINT OFF OF DUCT SMOKE DETECTORS
NO ACCESS TO VAV ROOM L-45, L-59
OK CEILING TILES PERIMETER PATIENT ROOM AREA 1B
01/25/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES NORTHSIDE OF BLDG. EAST OF SHAFT
STILL NEED TO SEE 1 MORE DAMPER IN THIS AREA
01/22/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED REMAINDER OF FIRE DAMPER ANGLES.
OK TO COMPLETE CEILING TILES BLDG 3A
WILL CHECK SENSING TUBES ON FIRE DAMPER TEST
01/18/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
BLDG 3A EXTEND SENSING TUBES OR PROVIDE SUPPORT.
CLEAN PAINT OFF OF DUCT SMOKE DETECTOR COVERS
WEST SHAFT FIRE DAMPER OPENING TOO LARGE
OK PARTIAL CEILING TILES
LEAVE OUT AROUND FIRE DAMPERS
01/15/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
3RD FLOOR BLDG A FINISH FIRE DAMPER ANGLES, ETC.
OK PARTIAL CEILING TILES
LEAVE OUT AROUND FIRE DAMPERS & DIFFUSERS WEST HALF
CHECK ALL FIRE DAMPERS IN ENTIRE BLDG.
01/03/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
AREA 1A OK CEILING TILES UP TO COM. ROOM
INSPECTED REMAINDER OF STEAM PIPING
12/28/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/19/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*