Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM01872
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2008 | MECHANICAL - INTERMEDIATE | Approved | ||
03/18/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 140 PSI TEST ON STEAM PIPING FROM RISERS TO HOSPITAL LOOP - OK TO INSULATE MANHOLE 1-4 |
|
02/07/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILING TILES AREA 3B EXCLUDING PHARMACY AND ELEVATOR AREA |
|
02/05/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 100 PSI TEST HOT WATER REHEAT TO VAV BOXES OK TO INSULATE 5B |
|
12/28/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* COMPLETE SUPPLY AND RETURN AIR IN COM. ROOM INSULATE LINEAR DIFFUSER CANS IN LOBBY INSULATE REHEAT PIPING NO2 - NO3 - P26 - P28 - P27 - P25, NORTH CORR |
|
12/19/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - NEED TO SEE FRAMED OPENINGS FOR FIRE/SMOKE DAMPERS - REMOVE INSULATION FROM OPENINGS - ACCESS DOORS MUST BE LARGE ENOUGH TO REPAIR DAMPERS |
|
12/14/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHILLED & HEATING WATER PIPING 4TH FLOOR OK TO INSULATE |
|
11/09/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK PERIMETER ROOMS 3RD FLOOR AREA B CHECKED BOTH SHOFTS AREA B |
|
11/06/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 160 PSI TEST STEAM PIPING MED. PRESSURE FROM 2ND FLOOR NEG. TIE IN TO 1ST FLOOR OR ROOMS OK TO INSULATE. CHECKED DUCTING 1ST FLOOR SHAFT A SIDE OK TO ENCLOSE SHAFT |
|
11/02/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/31/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED HEATING WATER LINES 1ST FLOOR AREA B OK TO INSULATE 120 PSI TEST IS OK |
|
10/26/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SMOKE DAMPERS INSTALLED PER SPECS |
|
10/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK AREA A 3RD FLOOR REMOVE INSULATION FROM FIRE & SMOKE DAMPERS |
|
10/17/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR SHAFTS PROVIDE FRAMING AROUND ALL WALL MOUNTED FIRE/SMOKE DAMPERS, ACCESS DOORS, DUCT SMOKE DETECTORS. OPENINGS MAY NOT BE FRAMED CORRECTLY. NEED INSTALL INSTRUCTIONS. |
|
08/27/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED LOW PRESSURE STEAM MAIN PIPING 2ND FLOOR TO PENTHOUSE. OK TO INSULATE 100 PSI 150 PSI TEST ON EAST CIRCUIT HEATING WATER 1ST FLOOR AND 3RD FLOOR AREA B |