Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
04/11/2008 MECHANICAL - INTERMEDIATE Approved
03/18/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
140 PSI TEST ON STEAM PIPING FROM RISERS TO HOSPITAL LOOP - OK TO INSULATE MANHOLE 1-4
02/07/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILING TILES AREA 3B EXCLUDING PHARMACY AND ELEVATOR AREA
02/05/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
100 PSI TEST HOT WATER REHEAT TO VAV BOXES
OK TO INSULATE 5B
12/28/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
COMPLETE SUPPLY AND RETURN AIR IN COM. ROOM
INSULATE LINEAR DIFFUSER CANS IN LOBBY
INSULATE REHEAT PIPING
NO2 - NO3 - P26 - P28 - P27 - P25, NORTH CORR
12/19/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- NEED TO SEE FRAMED OPENINGS FOR FIRE/SMOKE DAMPERS
- REMOVE INSULATION FROM OPENINGS
- ACCESS DOORS MUST BE LARGE ENOUGH TO REPAIR DAMPERS
12/14/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHILLED & HEATING WATER PIPING
4TH FLOOR OK TO INSULATE
11/09/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK PERIMETER ROOMS 3RD FLOOR AREA B
CHECKED BOTH SHOFTS AREA B
11/06/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
160 PSI TEST STEAM PIPING MED. PRESSURE FROM 2ND FLOOR NEG. TIE IN TO 1ST FLOOR OR ROOMS
OK TO INSULATE. CHECKED DUCTING 1ST FLOOR SHAFT A SIDE OK TO ENCLOSE SHAFT
11/02/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/31/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED HEATING WATER LINES 1ST FLOOR AREA B
OK TO INSULATE
120 PSI TEST IS OK
10/26/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SMOKE DAMPERS INSTALLED PER SPECS
10/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FOR SHEETROCK AREA A 3RD FLOOR
REMOVE INSULATION FROM FIRE & SMOKE DAMPERS
10/17/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR SHAFTS PROVIDE FRAMING AROUND ALL WALL MOUNTED FIRE/SMOKE DAMPERS, ACCESS DOORS, DUCT SMOKE DETECTORS. OPENINGS MAY NOT BE FRAMED CORRECTLY. NEED INSTALL INSTRUCTIONS.
08/27/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED LOW PRESSURE STEAM MAIN PIPING 2ND FLOOR TO PENTHOUSE. OK TO INSULATE 100 PSI
150 PSI TEST ON EAST CIRCUIT HEATING WATER 1ST FLOOR
AND 3RD FLOOR AREA B