Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM01872

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/08/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
2 TEST REPORTS RECEIVED FOR STERILIZER LOCATIONS
PROVIDE BACKFLOW CERTS ON ALL TESTABLE INTERNAL ASSEMBLIES FOR THIS PROJECT
PROVIDE CITY APPROVED PLAN REV. FOR ICE DRAINS
08/05/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
TEMPERING VALVE OK
MOP SINKS OK
PROVIDE INTERNAL BACKFLOW ASSEM. CERTS AND NEED TO VERIFY PLAN REV. FOR ICE MAKER DRAIN CONNECTIONS
07/31/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/11/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
STERILIZATION REPORT RECEIVED
04/09/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
L 3 AND 4 BABY WASHING SINK FAUCETS ARE OK
PROVIDE ACCESS AND CLEARANCES FOR BACKFLOW ASSEMBLIES AT STERILIZER LOCATIONS PER UPC SEC. 603.2.3
PROVIDE PROPER CONNECTIONS FOR QUATTRO SELECT SOAP DISPENSERS AT MOP SINK LOCATIONS. NO VALVES ALLOWED DN STREAM OF AVB
04/02/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- PENTHOUSE AND LEVEL 2 OK
- JUST NEED BACKFLOW CERTS.
- NEED TO CONFIRM TEMPERING VALVE ON EXISTING
HOT WATER
03/21/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
2A 2B 5B PENTHOUSE

LEVEL 5 MOST FIXTURES COMPLETE
PENTHOUSE & L2 NEED STRAINERS, GRATES, BACKFLOW CERTS, TRAP PRIMERS
03/19/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
LEVEL 3-A LAV REPLACEMENTS OK
LEVEL 1-A LAV REPLACEMENTS OK
LEVEL 1-B ALL FIXTURES OK
AIR BREAK ON HOSHIZAKI ICE MAKERS DO NOT APPEAR TO MEET UPC REQUIREMENTS OF AN AIR GAP
03/18/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
LEVEL 1B SOUTH CORRIDOR FIXTURES OK
LEVEL 4B FIXTURES OK EXCEPT FOR UNAPPROVED FAUCETS
03/17/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- UPC LISTING INFORMATION PROVIDED FOR KOHLER K15160 INDICATES THAT THIS FAUCET IS LISTED FOR USE AS A KITCHEN FAUCET.
- LISTING DOES NOT SPECIFY APPROVAL FOR PUBLIC AND/OR OTHER USES
- FAUCET DOES NOT PROVIDE BACKFLOW PROTECTION REQUIRED BY UPC T 6-2 FOR HIGH HAZARD APPLICATIONS SUCH AS BABY WASHING
- CAULK ALL CONNECTIONS AT WALLS AND FLOORS - TR AT ELEVATOR.
- WATER TESTS ON UNDER CABINET SINKS OK ..4-B EXCEPT NOT ALL SINKS HAVE BEEN INSTALLED
- ICE MACHINES/BEV. DISP. NOT YET INSTALLED
03/10/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
3-B FINAL INSP.

STILL NEED TO SEE 3RD PARTY LISTING INFORMATION FOR FAUCETS, TO VERIFY UPC CROSS CONNECTION CONTROL REQUIREMENTS AND PUBLIC USE APPROVAL. ALSO, NEED TO HAVE ALL BEVERAGE EQUIPMENT INSTALLED FOR FINAL.
TOILET RMS OK.
03/06/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
3-A FINAL PLUMBING OK EXCEPT FOR RMS 3-NO7 AND 3-NO9 HAVE UNAPPROVED LAVATORIES
RM 3 N52 HAS LEAK UNDER SINK
ALSO, I STILL NEED TO VERIFY HOT/COLD ORIENTATION AT ALL FIXTURES
03/04/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- 3B SINKS IN CABINETS WATER TESTS OK
- PROVIDE CODE LISTING FOR KOHLER
- SPRAY SPOUT TYPE FAUCETS LOCATED AT
BABY WASHING SINKS
02/21/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
3-A
UNLISTED LAVATORIES
UNSEALED TOILETS AT WALL CONN.
SLOPE ON TRAP ARMS
ALL EQUIPMENT INCLUDING COFFEE AND ICE TO BE INSTALLED
IDENTIFY RM #'S
02/20/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- STILL NEED ABV CEILING INSP. ON B 4 & 5
- STILL NEED TO OBTAIN FINAL APPROVAL OF ROUGH AND INTERMEDIATE INSPECTIONS BY PROVIDING CITY APPROVED PLAN REVISIONS FOR CHANGES AND FIXTURES ADDED
- TODAYS INSP. IS FOR LEVEL 1 BUILDING A
PROVIDE A UPC LISTING FOR LAVITORY BOWLS W/CORRUGATED EXTERIOR OVERFLOW
- HW SYSTEM HAS NOT BEEN ACTIVATED
12/28/2007 PLUMBING - FINAL Partial Approval EASTERN MOST 6" VALVE INSTALLED PER NOTE #39 ON REVISED C-5 PLAN