Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM01872
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
08/08/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 2 TEST REPORTS RECEIVED FOR STERILIZER LOCATIONS PROVIDE BACKFLOW CERTS ON ALL TESTABLE INTERNAL ASSEMBLIES FOR THIS PROJECT PROVIDE CITY APPROVED PLAN REV. FOR ICE DRAINS |
|
08/05/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* TEMPERING VALVE OK MOP SINKS OK PROVIDE INTERNAL BACKFLOW ASSEM. CERTS AND NEED TO VERIFY PLAN REV. FOR ICE MAKER DRAIN CONNECTIONS |
|
07/31/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/11/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* STERILIZATION REPORT RECEIVED |
|
04/09/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* L 3 AND 4 BABY WASHING SINK FAUCETS ARE OK PROVIDE ACCESS AND CLEARANCES FOR BACKFLOW ASSEMBLIES AT STERILIZER LOCATIONS PER UPC SEC. 603.2.3 PROVIDE PROPER CONNECTIONS FOR QUATTRO SELECT SOAP DISPENSERS AT MOP SINK LOCATIONS. NO VALVES ALLOWED DN STREAM OF AVB |
|
04/02/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - PENTHOUSE AND LEVEL 2 OK - JUST NEED BACKFLOW CERTS. - NEED TO CONFIRM TEMPERING VALVE ON EXISTING HOT WATER |
|
03/21/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 2A 2B 5B PENTHOUSE LEVEL 5 MOST FIXTURES COMPLETE PENTHOUSE & L2 NEED STRAINERS, GRATES, BACKFLOW CERTS, TRAP PRIMERS |
|
03/19/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* LEVEL 3-A LAV REPLACEMENTS OK LEVEL 1-A LAV REPLACEMENTS OK LEVEL 1-B ALL FIXTURES OK AIR BREAK ON HOSHIZAKI ICE MAKERS DO NOT APPEAR TO MEET UPC REQUIREMENTS OF AN AIR GAP |
|
03/18/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* LEVEL 1B SOUTH CORRIDOR FIXTURES OK LEVEL 4B FIXTURES OK EXCEPT FOR UNAPPROVED FAUCETS |
|
03/17/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - UPC LISTING INFORMATION PROVIDED FOR KOHLER K15160 INDICATES THAT THIS FAUCET IS LISTED FOR USE AS A KITCHEN FAUCET. - LISTING DOES NOT SPECIFY APPROVAL FOR PUBLIC AND/OR OTHER USES - FAUCET DOES NOT PROVIDE BACKFLOW PROTECTION REQUIRED BY UPC T 6-2 FOR HIGH HAZARD APPLICATIONS SUCH AS BABY WASHING - CAULK ALL CONNECTIONS AT WALLS AND FLOORS - TR AT ELEVATOR. - WATER TESTS ON UNDER CABINET SINKS OK ..4-B EXCEPT NOT ALL SINKS HAVE BEEN INSTALLED - ICE MACHINES/BEV. DISP. NOT YET INSTALLED |
|
03/10/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 3-B FINAL INSP. STILL NEED TO SEE 3RD PARTY LISTING INFORMATION FOR FAUCETS, TO VERIFY UPC CROSS CONNECTION CONTROL REQUIREMENTS AND PUBLIC USE APPROVAL. ALSO, NEED TO HAVE ALL BEVERAGE EQUIPMENT INSTALLED FOR FINAL. TOILET RMS OK. |
|
03/06/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 3-A FINAL PLUMBING OK EXCEPT FOR RMS 3-NO7 AND 3-NO9 HAVE UNAPPROVED LAVATORIES RM 3 N52 HAS LEAK UNDER SINK ALSO, I STILL NEED TO VERIFY HOT/COLD ORIENTATION AT ALL FIXTURES |
|
03/04/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - 3B SINKS IN CABINETS WATER TESTS OK - PROVIDE CODE LISTING FOR KOHLER - SPRAY SPOUT TYPE FAUCETS LOCATED AT BABY WASHING SINKS |
|
02/21/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3-A UNLISTED LAVATORIES UNSEALED TOILETS AT WALL CONN. SLOPE ON TRAP ARMS ALL EQUIPMENT INCLUDING COFFEE AND ICE TO BE INSTALLED IDENTIFY RM #'S |
|
02/20/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - STILL NEED ABV CEILING INSP. ON B 4 & 5 - STILL NEED TO OBTAIN FINAL APPROVAL OF ROUGH AND INTERMEDIATE INSPECTIONS BY PROVIDING CITY APPROVED PLAN REVISIONS FOR CHANGES AND FIXTURES ADDED - TODAYS INSP. IS FOR LEVEL 1 BUILDING A PROVIDE A UPC LISTING FOR LAVITORY BOWLS W/CORRUGATED EXTERIOR OVERFLOW - HW SYSTEM HAS NOT BEEN ACTIVATED |
|
12/28/2007 | PLUMBING - FINAL | Partial Approval | EASTERN MOST 6" VALVE INSTALLED PER NOTE #39 ON REVISED C-5 PLAN |