Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
08/12/2008 PLUMBING - PROGRESS Approved
03/28/2008 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
MET WITH SCOTT R.E. LEE, GUY ST. JOE'S HOSPITAL ABOUT BACKFLOW PROTECTION FOR ICE MACHINES
PROVIDE AN ACTUAL LISTING SHEET FOR THIS DEVICE OR CORRECT PROTECTION FOR BACKFLOW.
03/13/2008 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
ICE MAKER DOES NOT HAVE LISTING OR VISIBLE AIR GAPS
PROVIDE BACKFLOW PROTECTION PER UPC
KOHLER FAUCET SPECIFICATION SPECS A DECK MOUNTED VACUUM BREAKER
03/05/2008 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
NEW LAVITORY BOWLS W/CSA LISTING 113257 ARE OK TO USE
JACUZZI TUBS TEST OK
MAINTAIN ACCESS TO OVERFLOW AND PUMP
02/22/2008 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
INTERMEDIATE INSPECTIONS ARE COMPLETE BUT STILL NEED PLAN REVISIONS FOR ICE MAKER DRAIN BOXES
04/04/2007 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1" BLK STEEL FUEL LINES FOR EMERGENCY GENERATORS W/AIR TEST OK