Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T06CM01872
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | PLUMBING - PROGRESS | Approved | ||
03/28/2008 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* MET WITH SCOTT R.E. LEE, GUY ST. JOE'S HOSPITAL ABOUT BACKFLOW PROTECTION FOR ICE MACHINES PROVIDE AN ACTUAL LISTING SHEET FOR THIS DEVICE OR CORRECT PROTECTION FOR BACKFLOW. |
|
03/13/2008 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* ICE MAKER DOES NOT HAVE LISTING OR VISIBLE AIR GAPS PROVIDE BACKFLOW PROTECTION PER UPC KOHLER FAUCET SPECIFICATION SPECS A DECK MOUNTED VACUUM BREAKER |
|
03/05/2008 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* NEW LAVITORY BOWLS W/CSA LISTING 113257 ARE OK TO USE JACUZZI TUBS TEST OK MAINTAIN ACCESS TO OVERFLOW AND PUMP |
|
02/22/2008 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* INTERMEDIATE INSPECTIONS ARE COMPLETE BUT STILL NEED PLAN REVISIONS FOR ICE MAKER DRAIN BOXES |
|
04/04/2007 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* 1" BLK STEEL FUEL LINES FOR EMERGENCY GENERATORS W/AIR TEST OK |