Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T06CM01872

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2007 SITE - SEWER Approved IVRS - Inspection :*
BLD A 2-WAY CLEANOUT & HCS OK TERMINATE TRACER WIRE
10/24/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
- MANHOLE FROM MANHOLE #1 TO EXISTING OK
- 6" FROM MANHOLE #2 TO 1' FROM BUILDING
SEWER AIR TEST OK

1. SHALL SEE CORRECT TIE IN AT THIS POINT
AIR TEST MANHOLE #3 TO EXISTING OK
AIR TESTING THIS PROJECT OK MANDREL OK
MANHOLE VACUUM TESTING OK

1. NEED 2-WAY CLEANOUT AT BLD. A BUILDING DRAIN TO SEWER CONNECTION WITH INSPECTION. NEED CITY APPROVED REVISED PLAN WITH VERIFICATION OF GRADES TO FINAL.
2. NEED TO SEE CONNECTION AT TEMPORARY - EJECTOR PUMP LOCATION
10/23/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE #1 VACUUM TEST OK
MANHOLE #2 VACUUM TEST OK
MANHOLE #3 VACUUM TEST OK

MANHOLE #1 TO #2 AIR TEST OK
MANHOLE #2 TO #3 AIR TEST OK
MANHOLE #2 TO HCS 6" NOT READY HALL TEST
MANHOLE #3 TO EXISTING
MANDREL MANHOLE #1 TO #2 TO #3 OK
10/22/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
VACUUM TEST TO HOLD MINIMUM TIME
WITH 1" LOSS MAXIMUM
10/18/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
8" TIE IN FROM SOUTHEAST BUILDING LOCATION TO STUB FROM MANHOLE OK
10/17/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
PROVIDE APPROVED COUPLINGS FOR SEWER CONNECTION
10/16/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
MH 3 BASE OK. ALL PIPING HAS BEEN INSTALLED. STILL NEED TO WITNESS TESTING. STILL NEED APPROVED PLAN REVISIONS AND VERIFICATION OF GRADE.
10/15/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
PIPING FROM MH2 TO BUILDING OK,
PIPING FROM MH3 TO BUILDING
OK WILL INSPECT TIE IN AFTER SEWER IS COMPLETE
PIPING FROM MH2 TO MH3 OK
BASE NOT POURED
INSTALL WATER STOPS
10/10/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
DO NOT CONNECT TO BUILDING UNTIL SEWER AND MH TESTING IS COMPLETE
09/24/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
MH #2
WILL INSPECT MH INTERIOR AT TIME OF TEST
09/18/2007 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
MH #2 BASE COVERED
COORDINATE INSP. TO REMOVE LID FOR VISUAL INSP OF BASE INTERIOR
09/12/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
8' SEWER CONTINUATION TO 40' PAST 6" WATER MAIN
D1 INSTALLED 2' ABV WATER MAIN
INSTALL TRACER WIRE BEFORE COVERING
07/19/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
28' OF SEWER CONTINUED FROM LAST INSP.
SPLICE TO TRACER WIRE W/WEATHER RESISTANT WIRE NUT
04/20/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
130' INSTALLED S. OF MANHOLE #1
CALL FOR INSPECTIONS AS SOON AS PROGRESS IS CONTINUED
PROVIDE DETAIL 208
04/19/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1. PIPING BEING INSTALLED PER DELTA 6 REV ON UNAPPROVED CIVIL DRAWING.
2. MANHOLE #1 AND PIPING INSTALLED W/OUT INSP.
3. CALL FOR DAILY PROGRESS INSPECTIONS PRIOR TO COVERING.
4. PROVIDE WWM DETAIL 208
04/19/2007 SITE - SEWER Partial Approval FROM MANHOLE #1, APPROX 100' INSTALLED
OK TO COVER, FINAL APPROVAL REQUIRES TESTING AND VERIFICATION OF GRADE. CONTINUE TO CALL FOR INSPECTIONS.
01/18/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
GARY 488-6274 BFL AND MIKE LAMB EXCAVATION 631-6433
1. SITE SEWER BEING INSTALLED PER DELTA
REVISION #5 9/06
2. CITY APPROVAL OF REVISED PLAN REQUIRED.
3. ONE SECTION OF 8" SDR LAYED AND CONNECTED TO EXISTING MANHOLE #1
4. WATER STOP INSTALLED.
5. PLASTIC PIPING REQUIRES A GRN TRACER WIRE ATTACHED TO PIPE.
6. TEST ON PIPING REQUIRED.
7. THIS CAN BE DONE LATER.
8. CALL FOR DAILY PROGRESS INSPECTIONS
9. INSPECTIO OF MANHOLE BASES REQUIRED AND VACUUM TESTING OF NEW MANHOLE REQUIRED.
10. PROVIDE VERIFICATION OF GRADE OF PIPING.