Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Date Description Inspector Results Comments
04/09/2008 PLUMBING - MEDICAL GAS/TEST Approved IVRS - Inspection :*
03/04/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MED. GAS COLS. ON LEVEL 5 - OK
01/18/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1 INSTALLER ON OUTLET/INLET TRIM PLATES
12/06/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
02, MA AND VAC LINES PER CHANGE INSTALLED IN RMS 1-521 AND 1-522 W/PSI TEST OK
12/05/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
GREG CONNECTING VAC PUMPS
11/21/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PRESSURE TEST ON LEVEL 4
11/13/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1) LOG BOOK OK
11/08/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
11/06/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
11/02/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
10/31/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LEVEL 4 - 4 INSTALLERS
PIPING AIR NORTHEAST ZONE
PIPING AIR & O2 SOUTH ZONE.
KEEP LOG BOOK UP TO DATE
10/26/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval 3 INSTALLERS 4TH LEVEL, BRAZING VACUUM SOUTH & WEST,
INSTALLING AIR, O2 WEST
10/23/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PRELIMINARY TESTING O2, AIR, VAC - 5TH LEVEL
PIPING VAC 4TH LEVEL
10/17/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
FITTING ON 5TH LEVEL MOD AIR, BRAZING TO CONTINUE IN PM
10/15/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLERS WORKING ON 02 LEVEL 5 NE CORNER
10/10/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
10/08/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
VACUUM PIPING 5TH LEVEL PATIENT ROOMS & BRAZING
STARTED AIR PIPING 5TH LEVEL NORTH END
10/04/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
10/02/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
TEST ON MAINS TO 5TH LEVEL ZONE VALVES
09/28/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLERS ON 5TH FLOOR
09/26/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLING 02 MAIN TO S.ZONE VALVE BOX
09/24/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
09/20/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1) INSTALLING AND BRAZING ON 4TH ? AIR PIPING (NORTH) LOG BOOK CHECKED
09/18/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LEVEL 4 & 5 SEC B EAST
LOG BOOK CHECKED
MATERIAL STORAGE CHECKED
09/14/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
3B SOUTH UNDER TEST
LOGBOOK CHECKED
09/12/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
3 LEVEL 24 HR TEST COMPLETE.
LABELS COMPLETE
WORK STARTING ON 4
09/10/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
09/06/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
SEC 3A OK TO COVER
LOG BOOK OK
INSTALLERS WORKING ON VAC IN SEC 3B
08/31/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LEVEL 3A UNDER 24HR TEST
08/29/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval MED GAS PIPING LEVEL 3A UNDER TEST
08/27/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
CONTINUATION OF PIPING FOR WALL OUTLETS FOR 3A NICU
NORTH PER LOGBOOK DATED 8/27/07
08/22/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MED GAS MAINS COMPLETE W/LABELS AREA 3A
08/17/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG CHECKED
6 INSTALLERS WORKING IN AREA 3A
08/15/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
08/13/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG BOOK CHECKED
ISOLATION VALVES INSTALLED 3RD FL. A. INSTALLING VAC
08/09/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1ST FLOOR ALL AREAS
3RD FLOOR INFANT STAB AND NURSERY AND MAINS THROUGH LEVEL 5 UNDER 24 HR. TEST
08/07/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LDR EAST 1ST FLOOR B TEST ON WATER OK
PIPE INSULATION OK
08/03/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG BOOK OK
08/01/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
SEC. B OR #1 150 PSI TEST ON 02, N20, MA AND WAG
100 PSI ON VAR.
07/30/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MAINS INSTALLED TO LEVEL 5
INSTALLERS WORKING IN 1ST FLOOR OR'S
LOG BOOK CHECKED
07/26/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
07/24/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
07/19/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
07/17/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
07/13/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1ST FL SECT B
INFANT RES 1-519 UNDER TEST; O2, AIR, NITE AND VAC
ANES WORK RM 1-509 UNDER TEST; O2 AND AIR
3 INSTALLERS WORKING RECOVERY AREA 1-530
07/11/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
07/09/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS LDR SOUTH 1ST FLOOR
07/05/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PROGRESS LOOKS GOOD
SUPPORT BRANCH LINES CLOSE TO CONNECTION TO MAINS
07/02/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS WORKING. LOG BOOK OK.
1ST FLOOR LDR SOUTH AND RECOVERY AREA B
06/29/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/26/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG BOOK OK
PROGRESS OK
06/22/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/20/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
CACTUS MEDICAL APPROVAL OF TESTING
4 INSTALLERS WORKING
06/18/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
NURSERY, LDR EAST, TRIAGE AND INFANT STABILIZATION
UNDER TEST
06/14/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS WORKING ON OUTLET BOXES 1ST FLOOR SEC B
06/12/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
150 PSI TEST AIR & OXY, 100 PSI TEST VAC AT NURSERY AND INFANT STAB AREAS. LOG BOOK UP TO DATE.
06/08/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/06/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS WORKING ON 1ST & 3RD FLOOR
06/04/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
05/31/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
5 INSTALLERS WORKING
MED GAS MATERIALS STORED ON 3RD LEVEL AT NURSERY
05/29/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS INSTALLING OUTLET BOXES 1ST & 3RD
05/24/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
4 INSTALLERS WORKING IN LDR EAST AND NURSERY
LABEL INSTALLED DURING PROGRESS
05/22/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PROGRESS LOOKS GOOD
4 INSTALLERS WORKING
LOG BOOK UP TO DATE
05/17/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG BOOK UP TO DATE
4 INSTALLERS WORKING 6 DAYS PER WK
WORK PROGRESS OK
CONTINUE TO CALL FOR INSPECTIONS REGULARLY
05/08/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
ULTRA HIGH PURITY NITROGEN STORED ON 1ST LEVEL
100 PSI TEST FIRST LEVEL TRIAGE
MAINS THROUGH LEVEL 4
05/02/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
04/30/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG CHECKED, MATERIAL STORAGE CHECKED
5 INSTALLERS WORKING
PROGRESS LOOKS GOOD
04/26/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
04/20/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
2 INSTALLERS ON MAINS IN HALL L-41
04/19/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MED. GAS PROGRESS OK
3 INSTALLERS ON VAC
1ST FLOOR PART B HANGERS AND ZONE BOXES INSTALLED SINCE LAST INSP. LOG BOOK UP TO DATE.
04/05/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
2 INSTALLERS ON 8" VAC MAIN FROM PUMP LOCATION TO RISE UP TO 2ND FLOOR
03/22/2007 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MATERIALS STORED IN TRAILER AND GANGBOX ON 3RD LEVEL
HANGERS AND ZONE VALVES BEING INSTALLED
03/20/2007 PLUMBING - MEDICAL GAS/TEST Not ready for Inspection IVRS - Inspection :*
03043 APPROVED
PRE-CON 10 A.M.
JIM AND SCOTT W/RE LEE
STEVE W/CACTUS MEDICAL
GARY W/BFI
BRIAN FROM C.O.T
CALL FOR DAILY INSPECTIONS DURING INSTALLATION
KEEP A DAILY LOG BOOK AVAILABLE FOR INSPECTIONS.