Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM01872

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1ST LEVEL CLOSET FLANGES OK
02/21/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1B NORTH & EAST CORRIDOR CLOSET FLANGES OK
01/31/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/24/2008 PLUMBING - INTERMEDIATE Partial Approval IN WALL INSULATION LEVEL 5 OK
01/22/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPE INSULATION IN WALLS IN PATIENT RMS ON NORTH, EAST AND SOUTH CORRIDORS OK
12/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ABV CEILING INSPECTIONS WERE DONE DURING INTERMEDIATE INSP.
12/20/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
5TH FLOOR DOMESTIC WATER
LEVEL 5 DOMESTIC WATER OK FOR INSULATION
12/12/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TESTING COMPLETE
DOMESTIC WATER MAINS LEVEL 5 OK
LEVEL 4 PIPE INSULATION IN WALLS OK
12/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST FROM 4TH LEVEL FOR ROOMS 4-MO3B, 4-M73,
4-14, DWV 5TH LEVEL JANITOR 5-17, 5-I27, 5-I24, 5-101, 5-102, SINK 5-103, SINK 5-I33, DRAINAGE FOR PENTHOUSE PAGE P3.5B

1. SHALL TEST PENTHOUSE VENT THRU ROOF
12/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV AT RM 4 MO1B AND 4 MO2B W/TEST THRU ROOF OK
12/04/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PRE-CON W/BIRCH EXCAVATING AND SUNDT CORP.
FOR SITE WATER

PROVIDE APPROVED PLAN W/MECHANICAL PLAN REVIEW
LINE PSI OK FOR TESTING
LEAVE JOINTS EXPOSED FOR INSPECTION
11/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 4 PIPE INSULATION EAST OF CORR. 4-12 OK TO COVER
6" RWL CHANGE PER REDLINES W/TEST OK
11/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- DOMESTIC HW PIPE INSULATION IN WALLS ON BOTH SIDES OF CORR. 4-13 OK
- DWV W/TEST LEVELS 4 & 5 AT COLS 1.7 U THRU V AND @
COL. M OK
11/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVELS 4 & 5 SOUTH WING, BOTH SIDES OF CORRIDOR 12
DWV W/TEST THRU ROOF OK
LEVEL 4 DOMESTIC WATER OK TO INSULATE
11/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC B LEVEL 4 & 5 EAST WING BOTH SIDES OF CORRIDOR AND RMS M13-M16 ON SOUTH WING. DWV W/TEST THRU ROOF OK
11/14/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
4TH & 5TH LEVEL SEC B EAST WING DWV TEST OK
EXCEPT FOR RMS 17 & 19 B
11/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVELS 4 & 5, SEC B DWV W/TEST THROUGH ROOF
RMS BOTH SIDES OF CORR. 4-13 AND PAT. ROOMS 25-28
ALONG EAST WING OK
11/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 4 & 5 NORTH CORRIDOR RMS
DWV W/TEST THROUGH ROOF
11/05/2007 PLUMBING - INTERMEDIATE Cancelled
11/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
4 INSTALLERS ON LEVEL 4
LOGBOOK CHECKED
10/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 3 SHOWER VALVE INSTALLS & INSULATION OK
LEVEL 3 4" FLOOR DRAIN WATER TEST ROOM 3 - N25 OK
10/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV FROM 3RD LEVEL NORTH, EAST, WEST CORRIDOR BLD B
TO 4TH LEVEL REVENT OK
10/25/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
10/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL INSULATION IN WALL OK EXCEPT SHOWER AREAS
10/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 3 SEC B, DWV TESTING FROM 3RD TO 4TH
SOUTH AND WEST WINGS COMPLETE
DO NOT COVER UNTIL HW PIPING INSULATION IS COMPLETE
CALL FOR INSP. WHEN READY
10/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL B EAST SIDE DWV TESTING OK EXCEPT
AT 2" SINK NE
10/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST DWV 3RD LEVEL TO 4TH LEVEL 60" AFF
UNITS 3P24, 3P25, 3P26 & 4M24, 4M25, 4M26
10/04/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL VENTS AND 4TH LEVEL WASTE & VENT SEC 3B MIDDLE AREA, TESTS COMPLETE TO 5' ABV 4TH LEVEL
10/02/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL VENTS AND 4TH LEVEL WASTE
SEC B MIDDLE OK
10/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL VENTS AND 4TH LEVEL WASTE BETWEEN
COLS 13-14 AND N-8
09/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 3 SEC B DOMESTIC WATER OK TO INSULATE
08/29/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMESTIC WATER MAINS LEVEL 4B 100 PSI TEST OK
DOMESTIC WATER PIPING LEVEL 3A ROOMS OK TO INSULATE
08/22/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER MAINS LEVEL 3 UNDER TEST -- OK TO INSULATE
08/13/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMESTIC WATER MAINS 1ST FLOOR TO RISERS ON 3RD OK NEED TO SEE PIPE INSULATION
08/09/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LDR SOUTH 1ST FLOOR DOMESTIC WATER UNDER 100 PSI TEST AND HW INSULATION OK
1ST FLOOR SCRUB SINK DWV TEST OK
3RD FLOOR EXAM SINK NNO8 AND MEDS PYX SINKS OK
08/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WASTE & VENT MS 3NN06 OK
08/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLEASE REDLINE ICEMAKER DRAIN CONNECTIONS ON APPROVED PLANS
08/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. B MIDDLE DOMESTIC PIPING TESTED & INSULATED OK
LDR EAST RETEST AFTER MODIFYING LAV PIPING FOR
CORNER LAV
07/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- PROVIDE MIN. CLEARANCES FOR WATER CLOSETS
- DOMESTIC WATER PIPING COLS. 3.8-13 AND R-L OK FOR INSULATION.
- 100 PSI TEST
07/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMESTIC WATER IN WALLS JS 1-520 AND BETWEEN
COLS. R.4-U AND COL. 3-8-13
07/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE IN WALLS SECTION B 1ST FLOORS
PROVIDE PSI TEST
TESTS OK ALONG COL U MID-SECTION
06/29/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PART A DWV 1ST AND 2ND LEVEL ALONG COL 1.7 OK
TRAP ARM CORRECTIONS OK
INSTALL CLOSET FLANGES AFTER FINISHED FLOOR SECURE
ALL RWL TESTING COMPLETE
PERM CAP OR REMOVE TEST WYES
INSTALL CLEANOUT FITTINGS
06/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST AND 2ND FLOOR DWV TESTED TO 3RD LEVEL
MEZZ. CORRECTIONS OK
06/22/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DOMESTIC WATER PIPING 1ST FLOOR SEE B NORTH OF COL N WITH 100 PSI TEST OK
DWV SEC B NORTH OF COL. N TESTED TO 3RD FLOOR
OK EXCEPT LAVITORY TRAP ARM SIZE IS 1 1/2" MAX.
CLEANOUT EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS AND INSTALLED W/CO PLUG CLOSE TO FINISHED WALL.
06/14/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR A PIPE INSULATION COMPLETE. SEC B VENTING FOR 1ST & 2ND FLOOR BETWEEN COLS. 14 & 15 AND W-P TESTED TO ABV FLOOR LEVEL ? DRAIN PIPING FOR LEVEL 2 COLS 14-15 AND W-P TESTED ABV 3RD FLOOR
06/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOIL PIPING BELOW 3RD FLOOR
PART B BETWEEN COLS V THRU T AND 9 THRU 13
05/29/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TESTING COMPLETE ON ALL VENTS ON 1ST FLOOR PART A
2. TESTING COMPLETE ON DOMESTIC WATER PIPING 1ST & 2ND FLOORS PART A. OK TO INSULATE.
05/22/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
VENT IN WALLS AT #31 OK
TEST REST OF OVERHEAD VENTS
FIRST FLOOR PART B DWV COMPLETE
TEST THIRD FLOOR WASTE PIPING TO 10'
05/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2 OVERFLOW RES SEC A WITH TEST OK
HAVE APPROVED PLAN OPEN AND AVAILABLE PRIOR TO INSPECTION
LOG BOOKED CHECKED
05/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV 1ST FLOOR THRU 10' ABV 3RD FLOOR
BETWEEN COLS #12-13 AND U-Q
MAKE CLEANOUTS ACCESSIBLE.
TEST OK
PROVIDE AN INSPECTORS COPY OF APPROVED PLUMBING PLANS FOR INSPECTION PURPOSES.