Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01872

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - FINAL Approved PER FIELD NOTES BY RHOLLANDER ON SITE. SPECIAL INSPECTION REPORTS FOR OUTDOOR LIGHTING AND GFI TESTING ON SITE AND TO BE SUBMITTED TO CITY.
04/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WAITING ON EXTERIOR CANOPY LIGHTING
2. WAITING ON AS BUILT PLANS TO BE REVISED AND CITY STAMPS

*SUPPORT M/C CABLE ABOVE CEILINGS FOR PROJECTOR OUTLETS
*SUPPORT SPEAKER WIRES
04/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH VDV CABLING 725.6, 760.6, 770.6, 800.6, 300.11
2. WIRELESS TRANSMITTERS ATTACH TO GRID "ISB"
04/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED GENERATOR TEST REPORT
OK SERVICE TUNNEL
OK 5B 120 VOLT ELECTRIC

1. FINISH VDV WORK
04/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PHYSICAL PLANT
04/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
4B:
OK PREVIOUS ITEMS
OK PATIENT BEDS FOR LISTING MARKING

1. FINISH NURSES STATIONS
2. CIRCUIT DIRECTORIES
03/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED CK#3026 FOR $450.00

OK 1A/1B, 3A/3B, 2A/2B -- EXCEPT VDV CABLING EXPANSION JOINTS AND AS NOTED

FIRE PUMP MAIN DISCONNECT
FIRE PUMP CIRCUIT CONDUCTORS PER 655.6(B)
ICE MAKERS ARE LISTED UL
O.R ROOMS OK

1. (1A): CLASSROOMS PROJECTORS & SCREENS
2. (4B): SEE ATTACHED NOTES
3. VERIFY LISTING OF MED. GAS EQUIPMENT
4. VERIFY LISTING CHEMTRON VAC PUMP
5. LABEL DISCONNECT VAC PUMP
6. BASEMENT: FINISH FCO 05-2
FIRE ALARM WIRING
CONDENSATE PUMPS
7. PHYSICAL PLANT: STRAP CONDUITS
ADDRESS LABEL OUTSIDE DOOR
8. WILL NEED TO VERIFY LISTING OF ALL EQUIPMENT
03/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
5B:
1. FINISH - FIRE ALARM, VDV CABLING, PATIENT ROOMS
OK HALLS, LOBBY, OFFICES AND CONFERENCE ROOM ABOVE CEILING AS NOTED

1B:
1. HAVE ENGINEER PROVIDE A DIAGRAM FOR SUPPORT OF LAY IN FIXTURE WITHOUT GRID ROOM

OK 1B: SOUTH & WEST FINAL
03/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
3B: CENTER
1. SUPPORT WIRES FOR FIXTURES - COMM ROOM
2. FINISH PANEL DIRECTORIES PER 408.4 3B

OK 3B: EXCEPT AS NOTED FINAL
03/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 1B: ELEVATOR & ACCESS PASSAGE ABOVE CEILING
OK 3B: EXTERIOR PATIENTS ROOMS FINAL
03/18/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
5B WEST ABOVE CEILING
1. FINISH FIRE ALARM/SMOKE DETECTOR BOXES
2. FINISH ROOM 5B WEST
3. REMOVE BORDERS TO INSPECT LIGHTS & BOXES HALLS

4B: FINAL
1. BOXES MORE THAN 1/4" - 314.20
2. MISSING LIGHT FIXTURES - ROOMS
3. FINISH ROOMS
03/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH LABELING DEVICES
2. BOXES MORE THAN 1/4" - 314.20

OK MODULAR FURNITURE TRIAGE
03/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1A:
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
2. FINISH SUPPORTING CONDUIT ELECTRIC ROOM
3. LABEL CIRCUIT DIRECTORIES 408.4