Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01872
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | ELECTRIC - FINAL | Approved | PER FIELD NOTES BY RHOLLANDER ON SITE. SPECIAL INSPECTION REPORTS FOR OUTDOOR LIGHTING AND GFI TESTING ON SITE AND TO BE SUBMITTED TO CITY. | |
04/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WAITING ON EXTERIOR CANOPY LIGHTING 2. WAITING ON AS BUILT PLANS TO BE REVISED AND CITY STAMPS *SUPPORT M/C CABLE ABOVE CEILINGS FOR PROJECTOR OUTLETS *SUPPORT SPEAKER WIRES |
|
04/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING 725.6, 760.6, 770.6, 800.6, 300.11 2. WIRELESS TRANSMITTERS ATTACH TO GRID "ISB" |
|
04/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED GENERATOR TEST REPORT OK SERVICE TUNNEL OK 5B 120 VOLT ELECTRIC 1. FINISH VDV WORK |
|
04/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PHYSICAL PLANT |
|
04/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 4B: OK PREVIOUS ITEMS OK PATIENT BEDS FOR LISTING MARKING 1. FINISH NURSES STATIONS 2. CIRCUIT DIRECTORIES |
|
03/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED CK#3026 FOR $450.00 OK 1A/1B, 3A/3B, 2A/2B -- EXCEPT VDV CABLING EXPANSION JOINTS AND AS NOTED FIRE PUMP MAIN DISCONNECT FIRE PUMP CIRCUIT CONDUCTORS PER 655.6(B) ICE MAKERS ARE LISTED UL O.R ROOMS OK 1. (1A): CLASSROOMS PROJECTORS & SCREENS 2. (4B): SEE ATTACHED NOTES 3. VERIFY LISTING OF MED. GAS EQUIPMENT 4. VERIFY LISTING CHEMTRON VAC PUMP 5. LABEL DISCONNECT VAC PUMP 6. BASEMENT: FINISH FCO 05-2 FIRE ALARM WIRING CONDENSATE PUMPS 7. PHYSICAL PLANT: STRAP CONDUITS ADDRESS LABEL OUTSIDE DOOR 8. WILL NEED TO VERIFY LISTING OF ALL EQUIPMENT |
|
03/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 5B: 1. FINISH - FIRE ALARM, VDV CABLING, PATIENT ROOMS OK HALLS, LOBBY, OFFICES AND CONFERENCE ROOM ABOVE CEILING AS NOTED 1B: 1. HAVE ENGINEER PROVIDE A DIAGRAM FOR SUPPORT OF LAY IN FIXTURE WITHOUT GRID ROOM OK 1B: SOUTH & WEST FINAL |
|
03/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 3B: CENTER 1. SUPPORT WIRES FOR FIXTURES - COMM ROOM 2. FINISH PANEL DIRECTORIES PER 408.4 3B OK 3B: EXCEPT AS NOTED FINAL |
|
03/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 1B: ELEVATOR & ACCESS PASSAGE ABOVE CEILING OK 3B: EXTERIOR PATIENTS ROOMS FINAL |
|
03/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 5B WEST ABOVE CEILING 1. FINISH FIRE ALARM/SMOKE DETECTOR BOXES 2. FINISH ROOM 5B WEST 3. REMOVE BORDERS TO INSPECT LIGHTS & BOXES HALLS 4B: FINAL 1. BOXES MORE THAN 1/4" - 314.20 2. MISSING LIGHT FIXTURES - ROOMS 3. FINISH ROOMS |
|
03/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH LABELING DEVICES 2. BOXES MORE THAN 1/4" - 314.20 OK MODULAR FURNITURE TRIAGE |
|
03/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1A: 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 2. FINISH SUPPORTING CONDUIT ELECTRIC ROOM 3. LABEL CIRCUIT DIRECTORIES 408.4 |