Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
04/28/2008 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
11/19/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
11/16/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) GREEN STICKER ON CLEARED GEAR
2) RECEIVED PAPERWORK FOR TORQUE AND GFI TESTING
3) OK WALLS 1ST FLOOR AS MARKED
11/14/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/26/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK PANELS L3CRB1, L3CRB2, LCNB1, LCNB2, T3NB, T3CRB
OK WALL AS MARKED
09/19/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) BOND PANEL LOADS PER 517.14
2) OK PANELS AND TRANSFORMERS IN ELECTRIC ROOM 309 AS MARKED WITH GREEN STICKERS EXCEPT AS NOTED
08/30/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. BRANCH CIRCUITS TO ENTER SECTION/PANEL SERVED
05/02/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK TO ENERGIZE GENERATES TO TEST AND GENERATOR MAINS
1. WILL NEED GENERATOR REPORT

SEE GREEN STICKERS FOR APPROVED EQUIPMENT
04/30/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
04/27/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK CHILLER #2 - CLEAR TO ENERGIZE
PAT KENNEDY STARK/STURGEON 631-3815
WANT TO ENERGIZE CHILLER #1 TUESDAY MIDNIGHT.
04/09/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) RECEIVED PAPERWORK PER NUMBERS 1, 2, 4 & 6