Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM01872

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/19/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/18/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 4B NORTH, EAST & SOUTH
ELECTRIC

1. FINISH VDV CABLING
2. FINISH COMM ROOM
03/07/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
4B:
1. FINISH ROOM #4-M05, 4-M68

3B ELEVATOR LOBBY OK
1B COAX OK
4B 120V ELECTRIC OK
03/06/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/05/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/04/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CORRECTIONS MADE HALLWAY CEILINGS OK 1B
2. OK CEILINGS CENTER ROOMS 1B
02/26/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABLING 725.6, 318 FINISH NURSE CALLS
2. SUPPORT WIRES FOR EXIT SIGNS
3. CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8
02/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/21/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LID 5B ROOM 5-105
02/19/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
02/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/08/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/07/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/31/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
01/30/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
01/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/28/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/25/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT WIRES TO BE AS PER 300.11
2. NEED SUPPORT WIRES ON FIXTURES ALSO, OPPOSITE CORNERS
3. ATTACH FIXTURES TO GRID
4. OPEN JUNCTION BOX
5. EFFECTIVELY SUPPORT CABLES IN CLAMPS

OK 3A TILE AFTER CORRECTIONS
01/16/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/15/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. INDEPENDENTLY SUPPORT ELECTRICAL 300.11
2. SECURELY ATTACH FIXTURES TO GRID 410.16
3. SUPPORT WIRE NEEDED ALL FIXTURES - EXIT
4. SUPPORT VDV CABLING AS PER 725.6, 800.6, 760.6
01/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
PREVIOUS INSPECTION ITEMS CORRECTED
OK CEILING 1A