Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01872
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1B AT ELEVATORS ABOVE CEIL AND ACCESS PASSAGEWAY EXCEPT AS NOTED 1. PLEASE HAVE ARCHITECT/ENGINEER/PLAN REVIEWER VERIFY IF NFPA 20 5.12 APPLIES 2. FINISH FIRE ALARM ACCESS PASSAGE WAY OK TO CLEAR 350 N WILMOT FIRE PUMP *FINISH CIRCUIT CONDUCTOR TO INSPECT BEFORE ENERGIZING ROOF: 1. BOND BUSHINGS 250.97 2. LABEL DISCONNECT 3. NO MORE THAN 360 DEG. IN CONDUIT RUNS 4. FINISH VDV FIRE ALARM |
|
03/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2B: 1. BOND BUSHING NEEDED OVER 250V - 250.97 2. LABEL DISCONNECTS OK CONDUIT & LIGHTS OK PVC INTO TEP FOR FIRE PREP |
|
03/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PVC UNDERGROUND FOR FIRE PUMPS OK ELECTRIC IN MODULAR FURNITURE 1B(X4) 1. FINISH VDV CABLING IN MODULAR FURNITURE *NOTE: 695.6(B), 680.74 |
|
03/10/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4B: 1. FINISH VDV CABLING 2. MANUFACTURES CLIPS TO BE EFFECTIVE 410.16 3. SUPPORT WIRES NEEDED ON FIXTURES OK MODULAR FURNITURE WALLS 3B |
|
03/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 4B: SOUTH & WEST 1. VDV CABLING LAYING ON GRID SUPPORT AS PER 725.6, 800.6, 300.11 2. SECURE CABLING TO CABLE TRAY 3. FINISH DROP OF MC CABLE ROOM #4-M68 4. ATTACH FIXTURES TO GRID 410.16 MFG CLIPS TO BE EFFECTIVE 5. SUPPORT WIRES FOR EXIT LIGHTS 2A: 1. TIGHTEN LOOSE FITTINGS OK 2A CONDUIT, LIGHTS, BOXES |
|
03/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DO NOT TILE IB 1. COAX LAYING ON GRID SOUTH ROOMS, OK 1A MODULAR FURNITURE WALLS 4B 1. FINISH VDV HALLS & ROOMS ALSO, NURSE CALL SYSTEM 2. SUPPORT MC CABLE AS PER 300.11 OK ELECTRIC HALLS 4B EAST, 4B NORTH (& ROOMS) EXCEPT AS NOTED |
|
02/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRIC ROOMS (PANEL & XFMRS) FLOORS 4B & 5B |
|
02/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ELECTRIC ROOM A ON 4 75KVA XFMR GEC & BONDING JUMPER NOT SIZED PROPERLY. OK PANEL. 2. ELECTRIC RM. B ON 4 75KVA XFMR GEC & BONDING JUMPER NOT SIZED PROPERLY. OK PANELS 3. ELECTRIC RM. A ON 5 NEED BUSHINGS ON XFMR AND GEC NOT SIZED PROPERLY 4. PANELS OK ELECTRIC RM A ON 5 & B ON 5 5. INSTALL BUSHING ON XFMR CONNECTIONS & GEC NOT SIZED PROPERLY 6. OK SOFFIT NORTHWEST ELEVATOR LOBBY FLOOR 5B |
|
02/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1ST FLR CEILING 1. HAVE OPEN JUNCTION BOXES 2. LIGHTS MISSING TIE WIRE 3. CHECK ALL LIGHT ATTACHED TO GRID 4. UNABLE TO CHECK ALL ROOMS HAVE DOORS CLOSED & LOCKED 4B & 5B ELECTRIC CLOSETS 1. NEED TO HAVE XFMRS OPEN FOR INSPECTION AND APPROVED SET OF PLANS |
|
02/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3B: OK SOUTH HALL & NURSES STATION 5B: FINISH ROOM #5-105 OK 5B SOUTH & WEST ROOM SOFFITS OK BOTH STAIRWELL WALLS & LIDS |
|
02/07/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3B: 1. ATTACH FIXTURES TO GRID - MFG. CLIPS TO BE EFFECTIVE ALSO 2. SUPPORT WIRES NEEDED FOR EXIT SIGNS 3. VDV CABLING LAYING ON GRID & NOT SECURE UPON EXIT OF CABLE TRAY 5B: 1. SOFFITS DRYWALLED WITHOUT INSPECTION SOUTH ROOMS 2. JUNCTION BOXES TO BE ACCESSIBLE REMOVE DRYWALL TO INSPECT - THIS IS A REPEAT OFFENSE |
|
02/06/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
02/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT M/C 12" FROM CANS 2) OK FAMILY ROOM 5B 3) OK SOFFITS ROOMS 5B EAST 4) WHERE IS INSPECTIONS FOR STAIR WELLS |
|
01/31/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/30/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 5B NORTH EXCEPT FAMILY ROOM OK 5B NURSES STATIONS 3B: 1. VDV CABLING LAYING ON GRID 725.6 ALSO, UNSUPPORTED OK 3B PATIENT ROOMS OK 3B HALLS, EAST, WEST, CENTER AND NORTH FOR ELECTRIC EXCEPT AS NOTED DO NOT TILE |
|
01/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 5B CENTER SOUTH OK PVC IN ENTRY COLUMN |
|
01/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C CABLE AT SHALLOW STUDS -- FIREWALLS OK 5B SOUTH, WEST, EAST & NORTHEAST PERIMETER |
|
01/18/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK 5B SOUTH EXTERIOR WALLS 5B WEST: 1. LOOSE FITTINGS 2. NO MORE THAN 360 DEG. |
|
01/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 5B NORTH HALL & ROOMS 1. REMOVE DRYWALL TO INSPECT EXTERIOR WALL 5B SOUTH 2. PROTECT MC INSIDE CHANNEL OK 3A NORTH & CENTER HALLS TO TILE |
|
01/08/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY CABLE TRAY BONDING PER 392 2. NO FURTHER ABOVE CEILING INSPECTIONS UNDER 02035 USE CORRECT CODE 02036 3. FINISH #1 & #3 PREVIOUS INSPECTION |
|
01/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE HAVE 3RD PARTY REVIEWER ADD 02036 TO PERMIT 2. BOXES MORE THAN 1/4" IN TILE - 314.20 3. VDV CABLING TO BE AS PER 725.6 & 300.11 4. REMOVE BORDER TO INSPECT ELECTRIC 5. MARKING TO BE LEGIBLE ON BOXES OK LIGHTS 1A EXCEPT AS NOTED |
|
12/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ISOLATION ROOMS: L85, L86, L87 1. INSTALL VDV CABLING TO INSPECT METHODS PER 725.6, 800.6, 760.6 RECEPT/RECEIVING: 2. SUPPORT VDV CABLING PER 725. 6, 800.6, 760.6, 300.11, 392 3. ATTACH FIXTURES TO GRID 410.16 |
|
12/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 1ST FLOOR AS MARKED 2) OK ELECTRIC ROOM1-B |
|
12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONDUCTOR COLORS TO BE AS PER AMENDMENTS 210.5 (C) OK AS MARKED 4TH FLOOR |
|
12/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT MC CABLES AT SHALLOW STUDS - 4M58 OK ROOMS AS MARKED 4TH FLOOR |
|
11/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C CABLE AT SHALLOW STUDS - 330.17 2. NO MORE THAN 360 DEG. IN CONDUIT RUNS OK ROOMS AS MARKED - 4TH FLOOR |
|
11/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS 3 & 4 LEVEL AS MARKED OK CANS 4-M72 & 4M60 NURSE STATIONS 1. SUPPORT M/C CABLES 12" & CONDUITS 3' FROM BOXES 2. FILL UNUSED OPENING OF BOXES |
|
11/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 366.22 APPLIES 2) OK PANELS HEQDP 1 & 2, HCRDP, HIGRA, LICRA 1 & 2, TILCRA 3) OK 3RD LEVEL CANS IN ROOMS AS MARKED |
|
11/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK AS MARKED |
|
11/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANS IN SOFFIT AS MARKED 2) OK HARD LIDS ROOMS AS MARKED 3) DO NOT COVER WITHOUT INSPECTIONS |
|
11/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS AS MARKED |
|
10/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS BUILDING B AS MARKED ON PLANS |
|
10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK HARD LIDS 3RD FLOOR BUILDING "A" 2. NEED TO PROVIDE DEDICATED ELECTRICAL SPACE ABOVE ELECTRICAL EQUIPMENT PER NEC 110.26 (F)(1) |
|
10/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL AS MARKED 3A ALSO, HARD LIDS |
|
09/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BOXES OVERFILLED 2. PROTECT MC CABLE IN CHANNEL OK WALLS AS MARKED |
|
09/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT MC CABLE AT STUDS --- 330.17 OK WALL AS MARKED |
|
08/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT M/C CABLE IN STUDS 330.17 2. SUPPORT CONDUITS IN WALLS 3. PROPERLY SUPPORT MC STUDS OK WALLS AS MARKED -- 3RD FLOOR |
|
07/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AS MARKED ON PLANS |
|
07/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 3RD FLOOR PUTTY PADS FOR FIREWALL OK WALLS AS MARKED - 3RD FLOOR |
|
07/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PUTTY PADS ON BOXES BACK TO BACK IN FIREWALL OK WALLS AS MARKED ON OFFICE PLANS |
|
06/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALL INSULATION AS PER CAN MANUFACTURES INSTRUCTIONS. OK WALLS AS MARKED. |
|
06/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK AS MARKED |
|
05/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK AS MARKED ON PLANS 1. PLEASE VERIFY USAGE OF M/C CABLES |
|
05/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK ROOMS AS MARKED ON PLANS |
|
03/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. WILL NEED GFI TESTING 230.95, 515.17 (D) 2. VERIFY SELECTIVE COORDINATION 515.17 (C) 3. LASH CABLES AS PER MANUFACTURES INSTRUCTIONS 4. WILL NEED A LETTER OF TORQUE 5. DO NOT BUNDLE CONDUCTORS 310.10, 310.15 (B)(2) 6. CONDUCTOR TO ENTER SECTION SERVED 408.3 (A)(B) OK FROM PULL BOX OUT 60' 13 - 4" PVC W/RIDGID 90 DEG. 2 - 1 1/2 PVC W/RIDGID |