Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01872

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1B AT ELEVATORS ABOVE CEIL AND ACCESS PASSAGEWAY EXCEPT AS NOTED

1. PLEASE HAVE ARCHITECT/ENGINEER/PLAN REVIEWER VERIFY IF NFPA 20 5.12 APPLIES
2. FINISH FIRE ALARM ACCESS PASSAGE WAY
OK TO CLEAR 350 N WILMOT FIRE PUMP

*FINISH CIRCUIT CONDUCTOR TO INSPECT BEFORE ENERGIZING

ROOF:
1. BOND BUSHINGS 250.97
2. LABEL DISCONNECT
3. NO MORE THAN 360 DEG. IN CONDUIT RUNS
4. FINISH VDV FIRE ALARM
03/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2B:
1. BOND BUSHING NEEDED OVER 250V - 250.97
2. LABEL DISCONNECTS

OK CONDUIT & LIGHTS
OK PVC INTO TEP FOR FIRE PREP
03/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC UNDERGROUND FOR FIRE PUMPS
OK ELECTRIC IN MODULAR FURNITURE 1B(X4)

1. FINISH VDV CABLING IN MODULAR FURNITURE

*NOTE: 695.6(B), 680.74
03/10/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
4B:
1. FINISH VDV CABLING
2. MANUFACTURES CLIPS TO BE EFFECTIVE 410.16
3. SUPPORT WIRES NEEDED ON FIXTURES

OK MODULAR FURNITURE WALLS 3B
03/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
4B: SOUTH & WEST
1. VDV CABLING LAYING ON GRID SUPPORT
AS PER 725.6, 800.6, 300.11
2. SECURE CABLING TO CABLE TRAY
3. FINISH DROP OF MC CABLE ROOM #4-M68
4. ATTACH FIXTURES TO GRID 410.16 MFG CLIPS TO BE EFFECTIVE
5. SUPPORT WIRES FOR EXIT LIGHTS

2A:
1. TIGHTEN LOOSE FITTINGS

OK 2A CONDUIT, LIGHTS, BOXES
03/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
DO NOT TILE

IB
1. COAX LAYING ON GRID SOUTH ROOMS,

OK 1A MODULAR FURNITURE WALLS

4B
1. FINISH VDV HALLS & ROOMS ALSO, NURSE CALL SYSTEM
2. SUPPORT MC CABLE AS PER 300.11

OK ELECTRIC HALLS 4B EAST, 4B NORTH (& ROOMS)
EXCEPT AS NOTED
02/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRIC ROOMS (PANEL & XFMRS) FLOORS 4B & 5B
02/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ELECTRIC ROOM A ON 4 75KVA XFMR GEC & BONDING JUMPER NOT SIZED PROPERLY. OK PANEL.
2. ELECTRIC RM. B ON 4 75KVA XFMR GEC & BONDING JUMPER NOT SIZED PROPERLY. OK PANELS
3. ELECTRIC RM. A ON 5 NEED BUSHINGS ON XFMR AND GEC NOT SIZED PROPERLY
4. PANELS OK ELECTRIC RM A ON 5 & B ON 5
5. INSTALL BUSHING ON XFMR CONNECTIONS & GEC NOT SIZED PROPERLY
6. OK SOFFIT NORTHWEST ELEVATOR LOBBY FLOOR 5B
02/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1ST FLR CEILING
1. HAVE OPEN JUNCTION BOXES
2. LIGHTS MISSING TIE WIRE
3. CHECK ALL LIGHT ATTACHED TO GRID
4. UNABLE TO CHECK ALL ROOMS HAVE DOORS CLOSED & LOCKED

4B & 5B ELECTRIC CLOSETS
1. NEED TO HAVE XFMRS OPEN FOR INSPECTION AND APPROVED SET OF PLANS
02/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
3B: OK SOUTH HALL & NURSES STATION
5B: FINISH ROOM #5-105

OK 5B SOUTH & WEST ROOM SOFFITS
OK BOTH STAIRWELL WALLS & LIDS
02/07/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
3B:
1. ATTACH FIXTURES TO GRID - MFG. CLIPS TO BE
EFFECTIVE ALSO
2. SUPPORT WIRES NEEDED FOR EXIT SIGNS
3. VDV CABLING LAYING ON GRID & NOT SECURE UPON EXIT OF CABLE TRAY

5B:
1. SOFFITS DRYWALLED WITHOUT INSPECTION SOUTH ROOMS
2. JUNCTION BOXES TO BE ACCESSIBLE

REMOVE DRYWALL TO INSPECT - THIS IS A REPEAT OFFENSE
02/06/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
02/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT M/C 12" FROM CANS
2) OK FAMILY ROOM 5B
3) OK SOFFITS ROOMS 5B EAST
4) WHERE IS INSPECTIONS FOR STAIR WELLS
01/31/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
01/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
01/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 5B NORTH EXCEPT FAMILY ROOM
OK 5B NURSES STATIONS

3B:
1. VDV CABLING LAYING ON GRID 725.6 ALSO, UNSUPPORTED

OK 3B PATIENT ROOMS
OK 3B HALLS, EAST, WEST, CENTER AND NORTH
FOR ELECTRIC EXCEPT AS NOTED

DO NOT TILE
01/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 5B CENTER SOUTH
OK PVC IN ENTRY COLUMN
01/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE AT SHALLOW STUDS -- FIREWALLS
OK 5B SOUTH, WEST, EAST & NORTHEAST PERIMETER
01/18/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK 5B SOUTH EXTERIOR WALLS

5B WEST:
1. LOOSE FITTINGS
2. NO MORE THAN 360 DEG.
01/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 5B NORTH HALL & ROOMS

1. REMOVE DRYWALL TO INSPECT EXTERIOR WALL 5B SOUTH
2. PROTECT MC INSIDE CHANNEL

OK 3A NORTH & CENTER HALLS TO TILE
01/08/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY CABLE TRAY BONDING PER 392
2. NO FURTHER ABOVE CEILING INSPECTIONS UNDER 02035 USE CORRECT CODE 02036
3. FINISH #1 & #3 PREVIOUS INSPECTION
01/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE HAVE 3RD PARTY REVIEWER ADD 02036 TO PERMIT
2. BOXES MORE THAN 1/4" IN TILE - 314.20
3. VDV CABLING TO BE AS PER 725.6 & 300.11
4. REMOVE BORDER TO INSPECT ELECTRIC
5. MARKING TO BE LEGIBLE ON BOXES

OK LIGHTS 1A EXCEPT AS NOTED
12/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ISOLATION ROOMS: L85, L86, L87
1. INSTALL VDV CABLING TO INSPECT METHODS
PER 725.6, 800.6, 760.6

RECEPT/RECEIVING:
2. SUPPORT VDV CABLING PER 725. 6, 800.6, 760.6, 300.11, 392
3. ATTACH FIXTURES TO GRID 410.16
12/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROOMS 1ST FLOOR AS MARKED
2) OK ELECTRIC ROOM1-B
12/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONDUCTOR COLORS TO BE AS PER AMENDMENTS 210.5 (C)

OK AS MARKED 4TH FLOOR
12/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT MC CABLES AT SHALLOW STUDS - 4M58

OK ROOMS AS MARKED 4TH FLOOR
11/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE AT SHALLOW STUDS - 330.17
2. NO MORE THAN 360 DEG. IN CONDUIT RUNS

OK ROOMS AS MARKED - 4TH FLOOR
11/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 3 & 4 LEVEL AS MARKED
OK CANS 4-M72 & 4M60 NURSE STATIONS

1. SUPPORT M/C CABLES 12" & CONDUITS 3' FROM BOXES
2. FILL UNUSED OPENING OF BOXES
11/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 366.22 APPLIES
2) OK PANELS HEQDP 1 & 2, HCRDP, HIGRA, LICRA 1 & 2, TILCRA
3) OK 3RD LEVEL CANS IN ROOMS AS MARKED
11/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AS MARKED
11/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CANS IN SOFFIT AS MARKED
2) OK HARD LIDS ROOMS AS MARKED
3) DO NOT COVER WITHOUT INSPECTIONS
11/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS AS MARKED
10/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS BUILDING B AS MARKED ON PLANS
10/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK HARD LIDS 3RD FLOOR BUILDING "A"
2. NEED TO PROVIDE DEDICATED ELECTRICAL SPACE ABOVE ELECTRICAL EQUIPMENT PER NEC 110.26 (F)(1)
10/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL AS MARKED 3A ALSO, HARD LIDS
09/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BOXES OVERFILLED
2. PROTECT MC CABLE IN CHANNEL

OK WALLS AS MARKED
09/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT MC CABLE AT STUDS --- 330.17

OK WALL AS MARKED
08/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE IN STUDS 330.17
2. SUPPORT CONDUITS IN WALLS
3. PROPERLY SUPPORT MC STUDS

OK WALLS AS MARKED -- 3RD FLOOR
07/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS AS MARKED ON PLANS
07/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 3RD FLOOR PUTTY PADS FOR FIREWALL

OK WALLS AS MARKED - 3RD FLOOR
07/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PUTTY PADS ON BOXES BACK TO BACK IN FIREWALL

OK WALLS AS MARKED ON OFFICE PLANS
06/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL INSULATION AS PER CAN MANUFACTURES INSTRUCTIONS. OK WALLS AS MARKED.
06/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AS MARKED
05/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AS MARKED ON PLANS

1. PLEASE VERIFY USAGE OF M/C CABLES
05/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK ROOMS AS MARKED ON PLANS
03/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WILL NEED GFI TESTING 230.95, 515.17 (D)
2. VERIFY SELECTIVE COORDINATION 515.17 (C)
3. LASH CABLES AS PER MANUFACTURES INSTRUCTIONS
4. WILL NEED A LETTER OF TORQUE
5. DO NOT BUNDLE CONDUCTORS 310.10, 310.15 (B)(2)
6. CONDUCTOR TO ENTER SECTION SERVED 408.3 (A)(B)

OK FROM PULL BOX OUT 60'
13 - 4" PVC W/RIDGID 90 DEG.
2 - 1 1/2 PVC W/RIDGID