Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM01872
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | BUILDING - FINAL | Approved | ||
04/11/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* OK TCO FOR PATIENTS - TAKE VERY CLOSE LOOK AT ALL ACCESSIBLE RESTROOMS - JUSTIFY WHY ANY MULTI-USER RESTROOMS ARE NOT ACCESSIBLE. - PROVIDE DIRECTIONAL SIGNAGE TO NEAREST ACCESSIBLE TOILET, FOUNTAIN, ETC. IF FULL ACCESSIBILITY IS NOT MET. |
|
04/09/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* MUST HAVE 1, 2, 3 BY FRIDAY 1. VERTICAL GRAB BARS REQUIRED ALL ACCESSIBLE RESTROOMS @ W.C 2. SWEEPS @ ALL DOORS IN STAIRWELLS TO BE PROPERLY ADJUSTED 3. SMOKE SEALS @ ALL DOORS TO BE ADJUSTED 4. RESTROOMS IN LOBBIES NEED TO HAVE ACCESSBILE RESTROOM SIGNAGE & VERTICAL GRAB BAR 5. I STILL NEED TO TALKE TO PLUMBING, MECH. AND ELEC. INSPECTORS 6. QUICK DISCONNECT & SIGN WILL BE OK @ SOAP DISPENSER @ MOP SINKS (NO VALVES DOWN STREAM) |
|
04/03/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1. GUARD RAMP @ SE REQUIRES THAT YOU MAY NOT PASS A 4" SHEER 2. PAINT OUT CROSSINGS 3. REVISE SITE PLAN (ENGINEER MAY CALL ME) FOR INDICATED LOADING ZONES & TRUNC. DOMES & CROSSINGS 4. MOVE EXIT SIGN 1ST FLOOR ELEVATOR LOBBY 5. GRAB BARS 5TH FLOOR/ACCESSIBLE SIGNAGE 5TH FLOOR 6. 5TH FLOOR EXIT SIGN @ N.W STAIR TO BE DIRECTIONAL 7. EXIT SIGNS IN AREA AROUND STAIR B ARE CONFUSING (REMOVE 4 REPLACE 1) 8. PLEASE ARRANGE MEETING WITH ARCHITECT TO GO FLOOR BY FLOOR WITH BLDG. INSP. FOR EXIT SIGNS 9. PROVIDE SEALS & SWEEPS ON ALL FIRE AND SMOKE DOORS OR GIVE ME A CODE SECTION THAT EXEMPTS YOUR INSTALLATION CHECK NFPA80 |
|
03/21/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* TCO FOR STAFFING TO BE APPROVED WITH ELECTRICAL PARTIAL SATURDAY 3/22 1. VERTICAL GRAB BARS @ ACCESSIBLE RESTROOMS 2. 4TH FLOOR MAKE FIRE PILLOWS SMOKE TIGHT 3. 5TH FLOOR MAKE FIRE PILLOWS SMOKE TIGHT |
|
03/20/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* FOR TCO STAFF ONLY A. MAKE SURE ALL ADA ROOMS CORRECTLY IDENTIFIED WITH CORRECT HARDWARE 1. SEALS & SWEEPS ON ALL RATED DOORS ON 2HR WALLS AND STAIRWELLS AND SMOKE DOORS IN CORRIDORS (DOOR TO SMALL ROOMS OK) 2. PLEASE PROVIDE CABLE TRAY ROUTE AND REMOVE TILE ON BOTH SIDES OF SEPARATION DOORS 3. POST SIGNS "NOT AN EXIT" WHERE REQUIRED PROVIDE EMERGENCY EXIT ROUTE PLANS TO ANY STAFF 4. THRESHOLD IN BACK STAIR - ALL DOORS AND DOOR HARDWARE IN CORRIDORS |
|
03/07/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* ALL PROGRESS LOOKS GOOD TCO FOR STAFFING REQUIRES 1. FIRE ALARMS GOOD 2. FIRE SPRINKLER GOOD 3. GRAB BARS @ STAIRS 4. FINAL FIRESTOP @ DATA TRAYS |
|
02/28/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* YOUR SINKS ARE TOO HIGH YOUR TOILETS ARE TO FAR FROM WALLS |
|
01/30/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 5 COLUMN POURS @ EAST CANOPY OK |
|
01/11/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 5 EACH F7 FOOTINGS FOR CANOPY OK |