Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T06CM01872

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2008 SHEET ROCK NAILING Approved IVRS - Inspection :*
03/07/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
02/14/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
5TH FLOOR AREA B OK
02/04/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
01/30/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
ROCK @ CONNECTING CORRIDOR 3 A-B OK
01/16/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
01/11/2008 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
A-1 OK
01/09/2008 SHEET ROCK NAILING Not ready for Inspection IVRS - Inspection :*
12/11/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
AREA "B" - LEVEL 1: AREAS EXCEPT SOUTHWEST AREA SOFFITS - SE CORRIDOR (FIRE CORRIDOR) ENTRY & STAIRWELL AREA -- OK TO TAPE PROGRESS AREAS (*)

(*) - ENSURE ALL PENETRATIONS IN FIRE CORRIDORS ARE PROPERLY FIRE CAULKED.
11/21/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
NE LEVEL 3 OK TO TAPE
THIS IS NOT FIRE STOP
11/16/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
3RD FLOOR CORE OK TO TAPE EXCEPT @ PENETRATIONS
11/02/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
AREA A -- LEVEL 3

1. HAVE ALL FIRESTOP IN PLACE
2. OK TO TAPE EXCEPT AT PENETRATIONS IN GATED WALLS
10/26/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
AREA A
1. LEVEL 1 OK
2. LEVEL 3 HAVE ALL FIRESTOPS IN PLACE BEFORE CALLING FOR INSPECTION
07/06/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
THIS INSPECTION COVERS THE FOLLOWING AREA BLD "A"
EXTERIOR WALL FOR DENSGLASS EXTERIOR SHEATING
07/02/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
THIS INSPECTION COVERS FROM A-F/E23-E35
OK TO TAPE AREA A
05/01/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
THIS INSPECTION COVERS ONE SIDE OF TWO LAYER OF 5/8 ON THE SAME WALL ABOVE MENTIONED PLUS FIRE SEALANT ON DECK IN CONNECTION WITH THE WALL.
04/18/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
2 HOUR WALL @ LINES P.5/15 TO T/10 AT CEILING HEIGHT
DOWN 8' -- 2 LAYERS OF 5/8 SHEETROCK FIRE CAULK & FIRE TAPE AS PER PLANS.
03/15/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
MUST PROVIDE RFI FOR CHANGES ON WALL REGARDING 2HR FIRE RATED PARTITION FOR SMOKE TIGHT PARTITION.
02/23/2007 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
OK TO TAPE ROCK ON ONE SIDE