Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: FIREWALL/FIREBARRIER/FIRESTOP

Date Description Inspector Results Comments
04/03/2008 FIREWALL/FIREBARRIER/FIRESTOP Approved IVRS - Inspection :*
03/21/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
03/17/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1-B CORRIDOR - ELEVATOR AREA, WEST OF ELEVATORS
MED. GAS ROOM - ALL AREAS EXCEPT DATA TRAYS
03/13/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
EAST CORRIDOR & INTERIOR WALLS - 5TH FLOOR COMPLETE
03/11/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
5TH FLOOR N,W,S CORRIDORS EXCEPT FOR DATA LINES; CABLE LINES - UNABLE TO INSPECT INTERIOR ROOMS FLOORING MASTIC BEING APPLIED

631-1815 ROD
03/10/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
4TH FLOOR EXCEPT DATA TRAYS
03/07/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
03/04/2008 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
TELE/DATA LINES NOT PROPERLY FIRE CAULKED
DO NOT TILE AREAS UNTIL PROPER SEALING IS COMPLETE
4TH FLOOR CORRIDORS
02/29/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
OK TO TILE 1B

1. JOINTS @ 2H WALL WEST
2. CABLE TRAYS @ DOORS
3. CORRIDOR @ WEST BEHIND BATHROOM
02/28/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
AREA 1-B N 1/2 DONE (NOT P.8)
02/25/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
AREA 1-B NORTH OF P.8

A. CABLE TRAYS @ 2 HR LINE (P.8)
B. DUCTS IN C UTIL 1-518 & UTILITY CLOSET
C. DUCT F.DR LKR 1-510
D. 1 HR SECTION OF CORRIDOR 1-241
MUST USE INTUMESCENT ON ALL PENETRATIONS (RED STUFF)
02/21/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
02/14/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
OK TO CONTINUE & CLOSE STAIR REPAIRS
02/13/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
3B OK EXCEPT NEED TO RECHECK CABLE TRAYS @ SMOKE DOORS
02/08/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
02/07/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
OK BEHIND ELEVATORS 3A AND OK TO COVER NW STAIR LEVELS 4 AND 5
01/25/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1. A3 COMPLETE
2. NORTH CORRIDOR SMOKE WALLS ARE AT CORRIDOR
3. OTHER CORRIDORS: THE SMOKE SEAL IS IN ROOMS AND MUST BE INSPECTED AGAIN
01/16/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
A3 OK EXCEPT
1. LAUNDRY @ DUCT
2. RESTROOM BY STAFF LOUNGE
3. FORMULA PREP
01/11/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
A-1 OK
12/28/2007 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/07/2007 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1. LEVEL 1 AREA A OK
RECHECK ALL 6 & 8" NO HUB FIRE RISERS & SPRINKLERS AND ELEC ROOM
2. DO NOT USE "P" RINGS IN RATED WALLS