Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | ELECTRIC - FINAL | Approved | ||
| 07/23/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED DISCONNECTING MEANS FOR FIXTURES 410.63 (G) 2) PANEL SCHEDULE TO BE PER 408.4 3) ARC SHIELDS NEED 314.20 + 21 4) NEED PLANS REVISED FOR DELETION OF ROOMS-ELECTRIC RECEPTS AND LOT 29 5) FIXTURES ARE NOT CORD AND PLUG FROM MANUFACTURE |
|
| 08/26/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ELECTRIC TO SHELL 2) NO INTERIOR LIGHTING |