Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO INSTALL TILES |
|
| 05/21/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL PVC TO BE PRIMED 2. PROVIDE SADDLES ON ALL FLEX DUCT 3. HANGERS NOT TO EXCEED 4' ON FLEX DUCT 4. O.S.A DUCT PINCHED OF AT 90 DEG. BEND 5. ALL BENDS IN FLEX TO BE EQUAL TO 1 TIMES DIAMETER IN RADIUS 6. ALL PVC SUPPORTS NOT TO EXCEED 4' 7. PROVIDE TRAPPED OUTLET ON UNIT SECONDARY DRAIN 8. PROVIDE FLEX CONNECTORS AT UNIT SUPPLY AND CONNECTIONS |
|
| 04/24/2008 | MECHANICAL - INTERMEDIATE | Cancelled | IVRS - RI canceled |