Permit: T06CM01862

Parcel: 140260070


Addresses:

6194 S SEARS BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM01862

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK TO INSTALL TILES
05/21/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL PVC TO BE PRIMED
2. PROVIDE SADDLES ON ALL FLEX DUCT
3. HANGERS NOT TO EXCEED 4' ON FLEX DUCT
4. O.S.A DUCT PINCHED OF AT 90 DEG. BEND
5. ALL BENDS IN FLEX TO BE EQUAL TO 1 TIMES DIAMETER IN RADIUS
6. ALL PVC SUPPORTS NOT TO EXCEED 4'
7. PROVIDE TRAPPED OUTLET ON UNIT SECONDARY DRAIN
8. PROVIDE FLEX CONNECTORS AT UNIT SUPPLY AND CONNECTIONS
04/24/2008 MECHANICAL - INTERMEDIATE Cancelled IVRS - RI canceled