Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 09/10/2009 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1) A BOND WILL BE NEEDED FOR TEMP POWER FOR TEST 2) OBJECTIONABLE CURRENT AT SERVICE 250.6 |
|
| 09/10/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1. OK GROUNDING & BANDING FOR BLD. WATER, GAS 2. SERVICE NOT INSTALLED PER PLAN, REVISE PLAN OR INSTALL SERVICE EQUIP. AS INDICATED ON PLAN |