Permit: T06CM01844

Parcel: 12713078B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM01844

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLANS SHOW 1/2" DUCT LINER ON EXHAUST & 1" LINER ON SUPPLY & RETURN DUCT.
PROVIDE REVISION IF CHANGING.
CONDENSATE CANNOT TERMINATE ONTO PAVEMENT.
TERMINATE ALL CONDENSATES INSIDE THE BLDG & EXISTING UNITS.
PROVIDE AN APPROVED BASE FOR ALL EXISTING UNITS ON ROOF.
SUSPENDED ROUGH DUCT OK TO PROCEED.
06/12/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MINIMUM INSUL. WRAP UNDER BLDG. INSUL.
ENVELOPE IS R-5