Permit: T06CM01844

Parcel: 12713078B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM01844

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
WATER TEST PER APPROVED PLAN BASEMENT LEVEL OK
06/30/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER JUST STREET LEVEL SOUTH WALL
06/20/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
9067543 DON
INVERT ELEV. AT NORTH END IS 9 1/2" BELOW CEILING.
DISTANCE FROM MAIN TO FARTHEST WC IS 30'
1/8" PER FOOT ALLOWED ON 4"
UPC DOES NOT ALLOW A WC ON A COMBINATION WASTE & VENT.
EXISTING CAST IRON MAIN HAS BEEN REPLACED W/ABS
PROVIDE UNIFORM SLOPE ON MAIN
PROVIDE HANGERS AT 4'
06/13/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- ROUGH PLUMBING IS DENIED
- INVERT ELEVATION IS TOO SHALLOW TO PLUMB THESE FIXTURES.
- UPC REQUIRES 1/4" PER SLOPE ON ALL DRAINAGE PIPING
- FIXTURE VENT SHALL BE TAKEN OFF ABOVE FLOW LINE OF PIPE.
ALSO, WATER TEST REQUIRED.
HANGERS AT 4' INTERVALS.
- ABOVE FLOOR PIPING IN ALL AREAS EXCEPT AT SOUTH WALL SINKS AND CLOTHES WASHER IS OK.
- AT SOUTH WALL PROVIDE 1/4" PER FOOT SLOPE AND WATER TEST.
- DOMESTIC WATER SUPPLY SHALL BE 1 1/4" AT SERVICE.
- CLOSET FLANGES NOT INSTALLED.