Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM01844
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* WATER TEST PER APPROVED PLAN BASEMENT LEVEL OK |
|
06/30/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER JUST STREET LEVEL SOUTH WALL |
|
06/20/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 9067543 DON INVERT ELEV. AT NORTH END IS 9 1/2" BELOW CEILING. DISTANCE FROM MAIN TO FARTHEST WC IS 30' 1/8" PER FOOT ALLOWED ON 4" UPC DOES NOT ALLOW A WC ON A COMBINATION WASTE & VENT. EXISTING CAST IRON MAIN HAS BEEN REPLACED W/ABS PROVIDE UNIFORM SLOPE ON MAIN PROVIDE HANGERS AT 4' |
|
06/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - ROUGH PLUMBING IS DENIED - INVERT ELEVATION IS TOO SHALLOW TO PLUMB THESE FIXTURES. - UPC REQUIRES 1/4" PER SLOPE ON ALL DRAINAGE PIPING - FIXTURE VENT SHALL BE TAKEN OFF ABOVE FLOW LINE OF PIPE. ALSO, WATER TEST REQUIRED. HANGERS AT 4' INTERVALS. - ABOVE FLOOR PIPING IN ALL AREAS EXCEPT AT SOUTH WALL SINKS AND CLOTHES WASHER IS OK. - AT SOUTH WALL PROVIDE 1/4" PER FOOT SLOPE AND WATER TEST. - DOMESTIC WATER SUPPLY SHALL BE 1 1/4" AT SERVICE. - CLOSET FLANGES NOT INSTALLED. |