Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM01844
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2006 | ELECTRIC - ABOVE CEILING | Approved | PER EL FINAL | |
07/10/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OLD VDV CABELING TO BE AS PER 725.3 & 800.3 2. SUPPORT WIRES NEEDED FOR BOXES IN CEILING. 3. FINISH FIRE SPRINKLER ROW 4. VDV CABELING TO BE SUPPORTED 300.11 OK TO THE EXCEPT AS NOTED *NOTE CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 (MGR. OFFICE) |