Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01837
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
11/30/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #3 HAS NOT BEEN MET-DID NOT PUT DBL STUD REMOVE INSULATION AND PUT DBL STUD 2) MAS CLIPS AT S.E. CORNER OF GARAGE NOT NAILED TO SHEAR 3) ROOF EDGE NOT NAILED PROPERLY |
|
11/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEARNAILING AT GARAGE DOOR OPENING MISSING NAILS 2) SHEAR PANEL AT REAR PATIO NEEDS DBL STUD 3) S.W. CORNER SHEAR NEEDS TO BE ALL THE WAY TO THE CORNER TIE BOTH WALLS TOGETHER AND NEEDS A DBL STUD 4) NO ACCESS TO ROOF 5) NEED 2 H2.5 ON DBL GIRDERS 6) TIGHTEN ALL LOOSE ANCHOR BOLTS |