Permit: T06CM01821

Parcel: 141332340


Addresses:

8357 S HUNNIC DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM01821

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
07/14/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL OFF ALL FRIEZE BOARDS
2) CHANGE OUT GIRDER TRUSS HANGERS TO 16D'S
07/13/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DON'T COVER
2) FRIEZE BOARDS NOT NAILED
3) WRONG NAILS IN HANGERS
4) MISSED NAILS ROOF DECK
07/12/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS STILL MISSING PAGE
2) NAIL HOLDOWNS AT GARAGE ENTRY
3 NAIL HORIZONTAL JOINT IN SHEATHING
4) STOPPED INSPECTION-COMPLETE PRIOR REQUESTS
06/20/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE LAST INSP
2) 2 SETS OF PLANS, MISSING PAGE D-6
3) NAIL HORIZONTAL JOINT AT FRONT ENTRY
4) CHANGE OUT HANGERS DO NOT USE 8D NAILS IN HANGERS USE 16 SINKERS ON THIS HOUSE
5) NAIL FREIZE BLKS
06/08/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HUMP IN FLOOR 2ND FLOOR ABOVE GLU LAM
2) NEED SHEARWALL TO TOP CHORD CONNECTIONS
3) DBL STUDS UNDER GIRDER TRUSS, ALL TH WAY DOWN TO CONCRETE
4) MISSING WIND BRACE ON SOUTH WALL 1ST FLOOR
5) MISSING 3 P.A.'S AT REAR WALL
6) MISSED SHEAR WITH P.A. AT FRONT ENTRY