Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/24/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE ADD 02036 TO PERMIT 2. PROPERLY SUPPORT VDV CABLEING AS PER 725.3 & 6, 800.3 & 6 3. CORDS NOT ALLOWED ABOVE CEILING. 4. SUPPORT WIRES ARE NEEDED FOR CANS. |
|
| 11/16/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL NAIL PLATES AS NEEDED 2. SECURE/SUPPORT MC AS NEEDED - OK WALL COVER AFTER CORRECTIONS - OK UNDERGROUND COVER TO CASH WRAP/CONDIMENT ISLAND - OK DISPENSERS COVER @ ISLAND SLAB |
|
| 11/02/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TALKED ABOUT RACEWAYS AT PUMPS (EXISTING) AND THE DEPTH THEY ARE AT-CONTRACTOR WILL KICK THEM DOWN AS MUCH AS POSSIBLE TO GET CLOSER TO REQUIRED 24" DEPTH |