Permit: T06CM01811


Addresses:

7496 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
12/21/2006 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
1. BOND JUNCTION BOX - 250.148
2. LIGHTS NOT FULL CUT-OFF AS PER PLANS. WE HAVE
ABOUT A 30 DEG. UPWARD EXPOSER.