Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01800
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
01/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN UP NAILS THROUGH A.35 INTO TOP PLATES 2) GABLE RAFTER AT BACK PATIO NOT BEARING ON WALL 3) SET NAILS THROUGH GIRDER HANGERS 4) 4' SHEAR PANEL MISSING SOUTH GARAGE WALL 5) PROVIDE LADDER 6) MISSING INTERIOR SHEAR TRANSFER 7) STOPPED INSPECTION |
|
12/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY SUPER |
|
12/08/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTHING CORRECTED |
|
12/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEAR AT THE BACK OF HOUSE NOT PER SHEARWALL PLAN 2) NEED ONE MORE COIL STRAP PATIO COLUMN 3) NAILING ON SHEAR TRANSFER TO ROOF NOT NAILED PER DRAWINGS 4) EDGE BLOCK NAILING NEEDS NAILS 5) NEED TO GO BACK AND ADD STAPLES VARIOUS SPOTS ON ROOF |