Permit: T06CM01798

Parcel: 11005317A


Addresses:

3075 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
06/19/2007 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
06/18/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL PIPE HUB IN CORRECT DIRECTION OF FLOW
BELOW GRADE PIPING SHALL BE CONTINUOUSLY SUPPORTED
(SHADE)
CLEANOUT REQUIRED AT 135 DEG. CHANGE OF DIRECTION
06/14/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE UNIFORM SLOPE THROUGHOUT WITH NOT LESS THAN 1/8" PER FOOT
2) REMOVE DIRT FROM TOP OF PIPE FOR INSPECTION. SECURE TRACER WIRE TO PIPE PER STATE STATUE
3) 1' COVER EXPECTED FOR FINAL APPROVAL