Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/29/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - CORRECT CW TOUCHING METAL AT WALL LIGHT FIXTURE ABV LAV - OK TO COVER WALLS |
|
| 07/25/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE 10 PSI TEST ON GAS, PROTECT FROM SHARP METAL; TOP PLATE 2. PROVIDE LETTER FOR USE OF PEX. 3. INSTALL PER MANUFACTURES REQUIREMENTS WHICH INCLUDE CERTIFICATION OF INSTALLER, PROPER USE OF SUPPORTS THAT ARE DESIGNED FOR USE W/PEX. NO ADHESIVE TAPE ALLOWED INSULATION REQUIRES THE USE OF ARMAFLEX CONTACT ADHESIVE. OK TO INSULATE WALLS. RECALL FOR INSP. |
|
| 07/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV W/TEST THRU ROOF OK |