Permit: T06CM01798

Parcel: 11005317A


Addresses:

3075 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/07/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
04/27/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL PIPING W/TEST AND FOAM WRAPS
OK TO COVER
PROVIDE PLAN REVISION FOR FINAL APPROVAL
04/24/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. POST YOUR ADDRESS
2. TRAILER LOCKED
UNABLE TO ACCESS PLAN OR PERMIT
04/19/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UPPER TERMINAL MAIN HAS FLAT SPOTS.
2. SOUTHEASTERN WC IS FLAT.
3. USE REBAR CROSS BRACE IF NECESSARY TO SUPPORT BRANCHES AT FOOTINGS.
4. 2" BRANCH LINE ON EAST END IS FLOATING ON LARGE DIRT CLOGS.
5. SUPPORT BELOW GRADE PIPING CONTINUOUSLY W/CLEAN COMPACTED FILL.
6. LETTER FOR SLOPE & TYPE OF VENTING OK FOR CONTINUATION OF WORK, BUT PLAN SHALL BE REVISED PRIOR TO FINAL APPROVAL.
04/18/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BACKPITCH PRESENT IN SEVERAL LOCATIONS
SUPPORT PIPING W/COMPACTED DIRT
04/11/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEMP HBS REQUIRE VAC BREAKERS FOR USE
PROVIDE UNIFORM SLOPE IN ALL AREAS
REMOVE CHUNKS
1/4" PER SLOPE IS REQUIRED EXCEPT THAT 4" MAY BE INSTALLED AT 1/8" WITH PRIOR APPROVAL
CONVENTIONAL VENTING IS REQUIRED UNLESS STRUCTURAL CONDITIONS APPLY
REVISE PLAN IF INSTALLING AT LESS THAT 1/4" AND IF HORIZONTAL VENTING IS NECESSARY.
ALSO, REDLINE OR REVISE CHANGES SUCH AS LOCATION OF WASTE PIPING WHEN NOT PER PLAN.