Permit: T06CM01771

Parcel: 11207410B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/06/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
06/30/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
VENT ON CONDENSATE DRAIN TO BE DOWNSTREAM OF TRAP.
PROVIDE AN ELBOW AT BOTTOM & DIVERT WATER AWAY FROM STRUCTURE. CONDUIT NOT CONNECTED CORRECTLY TO ELEC. DISCONNECT.