Permit: T06CM01770

Parcel: 111071400

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PIGTAIL NEUTRAL FOR 3-WIRE HOMERUNS AT RECEPTACLE NEC 300.13B
2. HAVE SEVERAL OVERFILLED BOXES - NEC 110.3B, 314.16
3. BATH FAN NOT WIRED/MADE UP
4. NEED NAIL PLATES WHERE HOLE IS LESS THAN 1 1/4 FROM STUD FACE - NEC 300.4
5. IDENTIFY WHITE USED AS HOT - NEC 200.6

PARTIAL INSPECTION UNIT #4 ONLY
GO THROUGH ALL BEFORE CALLING IN
PLANS TO BE ON SITE