Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PIGTAIL NEUTRAL FOR 3-WIRE HOMERUNS AT RECEPTACLE NEC 300.13B 2. HAVE SEVERAL OVERFILLED BOXES - NEC 110.3B, 314.16 3. BATH FAN NOT WIRED/MADE UP 4. NEED NAIL PLATES WHERE HOLE IS LESS THAN 1 1/4 FROM STUD FACE - NEC 300.4 5. IDENTIFY WHITE USED AS HOT - NEC 200.6 PARTIAL INSPECTION UNIT #4 ONLY GO THROUGH ALL BEFORE CALLING IN PLANS TO BE ON SITE |