Permit: T06CM01761

Parcel: 115160480

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01761

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1. NO ANSWER @ DOORBELL - NEED INTERIOR ACCESS 9:55 AM
04/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO STRAP MC WITHIN 12" OF CEILING J-BOX
NEC 330.30 C
2. IDENTIFY WHITE CONDUCTOR USED AS HOT AT ALL TERMINATIONS NEC 200.7 (C)(1)
3. IN SWITCH BOX WRAP GROUND ALL THE WAY AROUND GROUND SCREW AND TIGHTEN NEC 110