Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01761
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. NO ANSWER @ DOORBELL - NEED INTERIOR ACCESS 9:55 AM |
|
04/20/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED TO STRAP MC WITHIN 12" OF CEILING J-BOX NEC 330.30 C 2. IDENTIFY WHITE CONDUCTOR USED AS HOT AT ALL TERMINATIONS NEC 200.7 (C)(1) 3. IN SWITCH BOX WRAP GROUND ALL THE WAY AROUND GROUND SCREW AND TIGHTEN NEC 110 |