Permit: T06CM01754

Parcel: 11460019C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01754

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/03/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. SUPPORT BOXES WITH M/C CABLE FROM BACK MOVEMENT.
2. FINISH EXHAUST FANS.
3. USE APPROVED M/C STRAPS & FITTINGS.
4. MISSING PLASTER RINGS.
5. PROTECT VDV CABLING AT TOP PLATE.
6. WE HAVE BROKEN M/C SHEATHING.
7. NO PLANS ON SITE.
05/03/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
1. CHECK VDV ON ABOVE CEILING INSPECTION.
2. NOTE: VDV CABLING NOT TO BE SUPPORTED OFF OF CONDUIT SUPPORT AT 6' SPACING.
NOTE: WE HVE PVC ABOVE CEILING IS THIS A PLENIUM?