Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01754
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/03/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1. SUPPORT BOXES WITH M/C CABLE FROM BACK MOVEMENT. 2. FINISH EXHAUST FANS. 3. USE APPROVED M/C STRAPS & FITTINGS. 4. MISSING PLASTER RINGS. 5. PROTECT VDV CABLING AT TOP PLATE. 6. WE HAVE BROKEN M/C SHEATHING. 7. NO PLANS ON SITE. |
|
05/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS 1. CHECK VDV ON ABOVE CEILING INSPECTION. 2. NOTE: VDV CABLING NOT TO BE SUPPORTED OFF OF CONDUIT SUPPORT AT 6' SPACING. NOTE: WE HVE PVC ABOVE CEILING IS THIS A PLENIUM? |