Inspection History Details
Permit: T06CM01748
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/24/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL OFF ELECTRIC HOME RUN FHA STRAPS |
|
| 07/20/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEEDS ALL CAULKING 2) EAST DWV AND H20 OK 3) FHA STRAP OVER BOXES AT ELECTRIC AND GAS MAINS 4) FINISH FIRE BLOCKING CHASE SOUTH OF ENTRY DOOR 5) BANG PLATE ELECTRIC IN ENTRY PONY WALL AND KITCHEN EAST WALL AND TRANS 6) NO WATER IN WEST DWV 7) FHA STRAP TOP PLATES AT ABS IN MASTER BATH SHEARWALL FOR OVER BORE 8) CAULK OPENINGS IN MASTER SHOWER AND FIREPLACE FIREBLOCKING |