Permit: T06CM01746


Addresses:

9976 E CALDERA PL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01746

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2006 FRAMING Approved IVRS - Inspection :*
07/13/2006 FRAMING Partial Approval IVRS - Inspection :*
07/12/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMIT VISIBLE
07/07/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN REDHEADS.
2. NEED ENGINEERED FIX FOR CONCRETE WHERE CABLES EXPOSED.
3. COMPLETE AT ENTRY AND FRONT WINDOW.
4. CAULK SCUPPERS AND PIPES
5. COMPLETE STAPLING WEST SIDE
6. NAIL STOP WIRE TOP PLATE SE CORNER L/R
7. ADD RECEP. SE CORNER FAMILY ROOM.
8. SUPPLY AIR TEST ONLY 8 LBS.
9. DWV TEST OKAY.
10. INSTALL NAILED FHA STRAPS WEST TOP PLATES CUT
FOR 2" ABS.
11. NAIL STOP SUPPLY LINES KITCHEN.
12. JUMPER BOX LYING IN TRUSSES EAST HALLWAY,