Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) NO PERMIT ON SITE-ENTER AT NEXT INSPECTION |
|
| 09/29/2006 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) CANNOT USE SPLIT BOLT TO SPLICE UFER CONDUCTOR PER 2002 NEC 250.64(C) |
|
| 09/27/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UFER REPAIRED WITH SPLIT BOLT |