Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/05/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO STREET ADDRESS 2. COMPLETE CONNECTION TO WATER HEATER OR REMOVE WYE FROM FLUE 3. ADD NIPPLE TO CONDENSATE DRAIN "T" TO RAISE ABOVE CUTOFF SWITCH 4. CONNECT ELECTRIC TO DISCONNECT 5. SECURE CAP TO B-VENT 6. CONNECT FURNACE GAS & ELECTRIC |