Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/18/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE 16D OR N16 (.0162 X 3 1/2 OR .0162 X 2 1/2) ON H.D.'S 2) RETRO H.D.'S IN 3 PLACES MARKED ON FLOOR WHERE SPAULED OUT |
|
| 07/12/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) LEDGERS AND BARGE BOARDS OK 2) USE 16 COMMONS OR N16 ON PA STRAPS 3) REPLACE SPAULED OUT PA STRAPS WITH RETRO HOLDOWNS |