Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM01722
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2007 | FRAMING | Approved | IVRS - Inspection :* | |
05/09/2007 | FRAMING | Partial Approval | IVRS - Inspection :* READING AS BUILT APPROVAL FOR PURLIN |
|
05/08/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) INSPECTIONS TO DEN AND BATH ONLY: PROVIDE GAS BOND 2) SUBMIT AS BUILT FOR ALL DEN ELECTRICAL CHANGES OR BUILD TO PLAN 3) TERMINATE EXHAUST VENT TO EXTERIOR 4) MISSING EXTERIOR GFCI TO BBQ GRILL |
|
05/07/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS PRESSURE TEST, DOES NOT HAVE ENOUGH PRESSURE TO TEST 2) NEED TO CHANGE ELECTRIC PLANS FOR BUILT IN CABINET OR INSTALL MANUFACTURER RECEPTACLE OUTLETS 3) NEED PROTECTION PLATES ON PEX LINES AT BATHROOMS 4) RE-LOCATED SMOKE DETECTOR IN HALLWAY 5) FIRE SEAL CUT OUTS IN TOP PLATE |
|
05/04/2007 | FRAMING | Cancelled | CANCELLED PER MARK OF CALEB CONST. #909-4042 | |
04/23/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) FRAMING DOEN WITH ALL INTERMEDIATE INSPECTIONS |
|
01/08/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL TRADES 2) PER DETAIL 3/A-11 MISSING PURLINS AND BLOCKING 3) SUBMIT AS BUILT OR BUILD TO PLAN |