Permit: T06CM01710

Parcel: 11005327C


Addresses:

2900 N COLUMBUS BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01710

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20 WALL & CEILING
2. BROKEN FIXTURE WHIP TO BE REPAIRED
3. ELECTRIC TO BE SUPPORTED AS PER 300.11
4. MISSING JUNCTION BOX COVER AND BOX OVERFILLED
5. FILL UNUSED OPENINGS IN BOXES -- NOT EMPTY FITTINGS
6. SUPPORT M/C ABOVE HARD CEILING

RECEIVED LETTER FROM ENGINEER