Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01710
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO TILE EXCEPT AS NOTED 1. SUPPORT OLD MC UP OFF OF GRID 2. SUPPORT OLD VDV CABELING AS PER 725.3 & 6 AND 800.3&6 3. SUPPORT NEW M/C ABOVE GRID 4. REVIEWED LETTER WAITING ON STAMP -- OK WALLS & HARD LID |
|
07/25/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS SUBJECT TO LETTER FROM ENGINEER FOR 1/2" CONDUIT PLANS CALL FOR 3/4" MIN. |
|
07/19/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS 2. SUPPORT CONDUITS AS PER CODE. 3. PREVENT DIEELECTRIC CONTACT 4. WHY IS BOX BELOW CEILING |