Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2008 | MECHANICAL - ABOVE CEILING | Approved | ||
| 10/06/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ITEMS DATED 9/18/08 4, 3, 5, 2, 6 OK VERIFY DRYER FLUE & VENTING FC-3, FC-4 DUCT PER PLANS |
|
| 10/03/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PROVIDE PROPER FALL ON CONDENSATE PIPING ON UNIT CLARIFY NEED FOR FIRE DAMPERS IN FIRE CORRIDOR |
|
| 09/18/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ANGLE FLANGE ON FIRE DAMPERS AND ACCESS DOORS 2. PROVIDE FLEX CONNECTORS AT AIR HANDLERS PER DETAIL 3 M2.01 3. PROVIDE STRAPS AND SADDLES PER DETAIL 1 M2.01 4. PROVIDE FLEX CONNECTIONS PER DETAIL 1 M2.01 5. PROVIDE PROPER RADIUS ON FLEX DUCT 6. PROVIDE CONDENSATE PIPING PER PLANS |