Permit: T06CM01697

Parcel: 10704006C


Addresses:

1564 W GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH BOILER
2. FINISH LAUNDRY CEILING
3. FINISH LABELING POOL PANEL

OK OUTSIDE POLES LIGHTS
10/27/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ATTACH CANS TO GRID
2. FIXTURE CLIPS TO BE EFFECTIVE
3. PLEASE VERIFY LISTING & LABELING FOR DRYERS
4. CORDS NOT ALLOWED 400.7 & 8 ABOVE CEILINGS
10/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PROTECT & SUPPORT VDV CABLING IN ATTIC AND DO NOT IMPEDE EGRESS

OK 2ND & 3RD FLOORS AND STAIRWELLS
10/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SECURELY ATTACH FIXTURES TO GRID 410.16
2. FINISH FLOOR BOXES

OK 1ST FLOOR SLEEPING UNITS
10/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHECK OUTLET PLACEMENT ROOM 224
10/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRIC 2ND FLOOR
10/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK WALLS 202, 302
AFTER BUILDING INSPECTOR

2ND FLOOR:
1. FINISH ROOM 202
2. NORTH STAIRWAY EXIT NOT WORKING
3. CHECK LAUNDRY

OK 2ND FLOOR EXCEPT AS NOTED 203-216

3RD FLOOR: OK 3RD FLOOR EXCEPT AS NOTED
1. FINISH ROOM 302
2. MISSING HALL LIGHTS
3. CHECK LAUNDRY
4. #312 OPEN NEUTRAL
10/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*

BOXES MORE THAN 1/4" -- 314.20
10/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
338-317

1. BOXES MORE THAN 1/4" - 314.20 WALLS & CEILINGS
2. USE APPROVED HARDWARE WITH DEVICES -
NOT DRYWALL SCREWS
3. CLEAN EXCESS FOREIGN MATERIAL FROM DEVICE TERMINALS 110.12 -- PAINT & DRYWALL SPLATTER
4. GROUND BOX PLATE