Permit: T06CM01697

Parcel: 10704006C


Addresses:

1564 W GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
11/04/2008 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
09/18/2008 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1. VERIFY DERATING PER 310.15 PANEL ACA & ACB
2. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM PANELS
3. FILL UNUSED OPENINGS
4. NEED ILLUMINATION B, HB, ACB
OK TO TEST ALL PANELS EXCEPT AS NOTED
5. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
6. PANEL HK MORE THAN 1/4"