Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2008 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 09/18/2008 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection :* 1. VERIFY DERATING PER 310.15 PANEL ACA & ACB 2. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM PANELS 3. FILL UNUSED OPENINGS 4. NEED ILLUMINATION B, HB, ACB OK TO TEST ALL PANELS EXCEPT AS NOTED 5. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 6. PANEL HK MORE THAN 1/4" |