Permit: T06CM01696

Parcel: 13707035U

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T06CM01696

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2009 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
LAST PRE-GROUT BY G.DABBS TRASH ENCLOSURE
11/12/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
INTERIOR & EXTERIOR WALLS TOP OUT

1. SPECIAL INSPECTED
2. NON-COMPLIANT ISSUES RESOLVED
PER WIRA ENGINEER OF RECORD
10/22/2008 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
NON-COMPLIANT ISSUES FROM SPECIAL INSPECTION
NEED TO BE ADDRESSED BY ENGINEER IN WRITING
10/21/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
5TH LIFT CMU WALLS @ BLDG. #2 FROM 16'0" TO 20'0"
OK TO GROUT
10/20/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12' TO 16'
OK TO GROUT WITH SPECIAL INSPECTION
10/17/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
8' TO 12' SPECIAL INSPECTED OK TO GROUT
10/14/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. BLDG. 2 MIDDLE AND SOUTH UNIT 2ND LIFT - OK TO GROUT
10/08/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. 2ND LIFT NORTH APT. ONLY
2. 9/12/08 INSPECTED INTERIOR FOOTINGS REBAR IN PLACE
3. NEED REPORT FROM WESTERN TECH. THAT
NON-COMPLIANCE ISSUES WERE TAKEN CARE OF
09/25/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CMU WALL TO 4' EXCEPT SPRINKLER ROOM

TERRACON SPECIAL INSPECTED