Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01695
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* A REFEE MAY BE ASSESSED PER ADMIN. CODES FINISH PREVIOUS ITEMS |
|
| 06/15/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 06/11/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE OR FLUSH AT COMBUSTIBLES - 314.20 2. GROUND FIXTURE HARDWARE 3. PROVIDE RANGE ANTI-TIP 4. PROPERLY IDENTIFY UNGROUNDED CONDUCTORS AT WATER HEATER AND AC'S 5. SMOKE DETECTORS TO BE ARC FAULT PROTECTED IN BEDROOMS - 210.12 6. PANEL SCHEDULES TO BE AS PER 408.4 7. ALL OUTDOOR RECEPTACLES TO BE GFCI PROTECTED 8. PLEASE PROVIDE SMOKE DETECTOR INSTRUCTIONS TO DETERMINE LOCATIONS 9. MAINTAIN WORKING CLEARANCES AT AC DISCONNECTS 110.26 10. GROUND METAL JUNCTION BOXES |
|
| 06/09/2009 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 05/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WAITING ON BOND DECISION |