Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01695
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL ITEMS ON SHEET HAVE BEEN TAKEN CARE OF ON FIRST BUILDING |
|
| 01/05/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED M/C CONNECTORS NOT ROMEX 2) USE BUSHING FOR CONDUCTOR LARGER THAN #8 352.46 & 300.4 3) SUPPORT M/C CABLES WITHIN 12" OF FITTINGS 4) PROTECT M/C CABLES IN SHALLOW WOOD STUDS 5) SUPPORT VDV CABLING PER 725.24 & 800.24 6) PROPERLY GROUND METAL BOXES 7) BOX OVER FILLED 8) FILL UNUSED OPENING IN PANELS 9) PLANS CALLL FOR 22K EQUIPMENT-PLEASE VERIFY ALL PANELS 10) SEPERATE GROUNDS AND NEUTRAL PANEL "S" 250.24 |
|
| 12/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEPARATE NEUTRALS AND GROUNDS INTERIOR PANELS 2. REPLACE DAMAGED MC CABLE UNDER PANEL UNIT #2 3. PLANS CALL FOR 200 AMP. PANELS, COPPER FEEDERS IN CONDUIT 4. RESUPPORT RISER CONDUIT AND GROUND WIRE 5. DO NOT REMOVE STRANDS OF WIRE TO MAKE FIT IN LUG AT SERVICE 6. BOND NEUTRAL SEE COVER OF SERVICE |