Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01671
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. POWER CENTERS FOR WALK LIGHTS TO BE MINIMUM 12" ABOVE GRADE - NEC 110.3B 2. PLANS STILL NEED TO BE REVISED TO SHOW ACTUAL SCOPE OF WORK 3. SITE UNDERGROUND COVERED WITHOUT INSPECTION |
|
10/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE A SEALED LETTER FROM THE ARCHITECT OF RECORD CONCERNING ANY CHANGES TO APPROVED PLAN 2) FINISH WIRING FOR PHONE/TV AT SERVICE LOCATION 3) REMOVE TEMPORARY SERVICE 4) IDENTIFY POOL PANEL AT SERVICE (NOT JUST ADDRESS) 5) SERVICE CONDUCTORS TO BE MINIMUM 10' ABOVE GRADE NEC 230.24 B 6) FINISH ALL SITE ELECTRICAL, I.E. CANOPY LIGHTING, GATE MOTORS ETC. 7) OK POWER TO POOL PANEL FOR THE PURPOSE OF TESTING. POOL IS NOT TO BE OCCUPIED BEFORE APPROVAL. INSTALL LOCK ON GATE TO KEEP UNAUTHORIZED PEOPLE OUT DURING CONSTRUCTION |
|
09/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING CONDUCTORS FOR MAST'S ARE UNDERSIZED NEC 250.102C 2. BONDING CONDUCTOR TO ENTER ENCLOSURE BELOW LIVE PARTS -- NEC 110 3. STILL NEED TO PROVIDE PHYSICAL PROTECTION FOR SERVICE -- NEC 110.27B 4. STILL NEED TO COMPLETE #1, 2, 4, 6, 7, 8, 9, 10 FROM PREVIOUS INSPECTION - A CALL FROM THE ENGINEER (JOHN GOMEZ) IS FORTHCOMING CONCERNING NEC 250.32 NEED TO PAY REINSPECTION FEE SINCE OTHER CORRECTIONS NOT COMPLETED |
|
07/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL SERVICE INSPECTION ONLY 1. NEED AN EQUIPMENT GROUND RAIN WITH FEEDERS TO SUB-PANELS -- NEC 408.20, 250.134B, 250.32B 1,2 2. REVISE SERVICE ONE LINE DIAGRAM AND FAULT CALCULATIONS FOR OVERHEAD SERVICE AND SERVICE CONDUCTORS USED - SERVICE IS NOT PER PLAN 3. BOND SERVICE MAST'S - NEC 250.92 4. IDENTIFY ALL SERVICE DISCONNECTS - NEC 230.70 B 5. PROVIDE PHYSICAL PROTECTION FOR SERVICE FROM VEHICULAR TRAFFIC - NEC 110.27 B (BOLLARD ETC) 6. PROVIDE POINT OF ATTACHMENTS FOR SERVICE DROPS NEC 230.26, 230.54C 7. NEED MINIMUM CLEARANCE ABOVE GRADE FOR SERVICE CONDUCTORS - NEC 230.24B 8. IDENTIFY SERVICE NEUTRALS OUT OF WEATHERHEAD NEC 200.6B 9. UNITS TO BE TRIMMED OUT NO OPEN WIRING 10. NEUTRALS AND GROUND TO BE SEPARATED IN SUB-PANELS - 250.24 A5 PROVIDE SUB-PANELS WITH AN EQUIPMENT GROUND - SEE CORRECTION #1 |