Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM01671

Parcel: 125115260


Addresses:

3630 E 3RD ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01671

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. POWER CENTERS FOR WALK LIGHTS TO BE MINIMUM 12" ABOVE GRADE - NEC 110.3B
2. PLANS STILL NEED TO BE REVISED TO SHOW ACTUAL SCOPE OF WORK
3. SITE UNDERGROUND COVERED WITHOUT INSPECTION
10/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE A SEALED LETTER FROM THE ARCHITECT OF RECORD CONCERNING ANY CHANGES TO APPROVED PLAN
2) FINISH WIRING FOR PHONE/TV AT SERVICE LOCATION
3) REMOVE TEMPORARY SERVICE
4) IDENTIFY POOL PANEL AT SERVICE (NOT JUST ADDRESS)
5) SERVICE CONDUCTORS TO BE MINIMUM 10' ABOVE GRADE NEC 230.24 B
6) FINISH ALL SITE ELECTRICAL, I.E. CANOPY LIGHTING, GATE MOTORS ETC.
7) OK POWER TO POOL PANEL FOR THE PURPOSE OF TESTING. POOL IS NOT TO BE OCCUPIED BEFORE APPROVAL. INSTALL LOCK ON GATE TO KEEP UNAUTHORIZED PEOPLE OUT DURING CONSTRUCTION
09/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING CONDUCTORS FOR MAST'S ARE UNDERSIZED
NEC 250.102C
2. BONDING CONDUCTOR TO ENTER ENCLOSURE BELOW LIVE PARTS -- NEC 110
3. STILL NEED TO PROVIDE PHYSICAL PROTECTION FOR SERVICE -- NEC 110.27B
4. STILL NEED TO COMPLETE #1, 2, 4, 6, 7, 8, 9, 10 FROM PREVIOUS INSPECTION - A CALL FROM THE ENGINEER
(JOHN GOMEZ) IS FORTHCOMING CONCERNING NEC 250.32

NEED TO PAY REINSPECTION FEE SINCE OTHER CORRECTIONS NOT COMPLETED
07/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL SERVICE INSPECTION ONLY
1. NEED AN EQUIPMENT GROUND RAIN WITH FEEDERS TO SUB-PANELS -- NEC 408.20, 250.134B, 250.32B 1,2
2. REVISE SERVICE ONE LINE DIAGRAM AND FAULT CALCULATIONS FOR OVERHEAD SERVICE AND SERVICE CONDUCTORS USED - SERVICE IS NOT PER PLAN
3. BOND SERVICE MAST'S - NEC 250.92
4. IDENTIFY ALL SERVICE DISCONNECTS - NEC 230.70 B
5. PROVIDE PHYSICAL PROTECTION FOR SERVICE FROM VEHICULAR TRAFFIC - NEC 110.27 B (BOLLARD ETC)
6. PROVIDE POINT OF ATTACHMENTS FOR SERVICE DROPS
NEC 230.26, 230.54C
7. NEED MINIMUM CLEARANCE ABOVE GRADE FOR SERVICE CONDUCTORS - NEC 230.24B
8. IDENTIFY SERVICE NEUTRALS OUT OF WEATHERHEAD
NEC 200.6B
9. UNITS TO BE TRIMMED OUT NO OPEN WIRING
10. NEUTRALS AND GROUND TO BE SEPARATED IN SUB-PANELS - 250.24 A5 PROVIDE SUB-PANELS WITH AN EQUIPMENT GROUND - SEE CORRECTION #1