Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM01671
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
07/02/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER RACEWAYS & GROUND RODS AT SERVICE |
|
06/29/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
03/27/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. FROM FRONT OF BUILDINGS TO WEST SIDE OF PROPERTY NO BENDS. LARGE SWEEP. 2. FROM BUILDING #1 1 - 2 1/2" AND 2 1" PVC 180 DEGREES OF BENDS LENGTH OF 30' FROM BUILDING. |
|
01/12/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* WE HAVE REDUCED RUNS TO 270 DEG. |
|
01/08/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* WE NOW HAVE 315 DEG. IN SOME RUNS - NO MORE THAN 360 DEG. ALLOWED. |
|
12/29/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1 1/4" FOR POOL 2) OK 2 1/2" PVC BACK UNIT UP TO 5TH UNIT IN TRENCH (10 UNITS) 3) NOTE: YOU HAVE 225 DEGREE ALREADY IN RUN 4) NOTE: INSTALL MARKER TAPE PER 300.5 |
|
12/28/2006 | ELECTRIC - UNDERGROUND | Cancelled | CANCELLED PER WARREN OF OLLANIK CONST. #260-0047 | |
12/28/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |