Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01666
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
06/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH NAILS IN 2ND FLOOR HIP HANGER 2) NAILS AT GIRDER BEHIND BLKS WHERE THEY CHANGED OUT 2ND FLOOR ROOF AT VERT DUCT CHASE 3) NAIL STUD TO PLATE CLIP EXT. S/EAST CORNER 2ND FLOOR 4) FROM LAST INSPECTION BLOCK ALL OSB TURNED PARALLEL TO TRUSS 5) TRUSS REPAIR FOR NOTCH CLOSER THAN 24" TO HEEL JOINT 6) NO PLAN ON SITE |
|
06/15/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WRONG NAILS IN ALL HANGERS ROOF (CANNOT USE 8D IN ANY LOAD BEARING HANGER, HANGER NAILS START 10D MINIMUM 2) CONNECT ALL SHEARWALLS TO TRUSS BOTTOM CHORD PER PLAN 3) INSTALL LU 24 HANGERS AT GARAGE SHED ROOF TO 3 1/8" GLU LAM PER PLAN 4) BLOCK AND NAIL FLOOR DECK AT 6" REPAIR 5) BLOCK ALL OSB AT ROOF OSB TURNED WRONG WAY |