Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01652
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
11/15/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) CHECK AT INTERMEDIATES |
|
10/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | NO CORRECTION WERE MADE FROM PRIOR INSPECTION | |
10/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO ROOF AND LATH 2) FLOOR NOT SCREWED, TACKED ONLY 3) ADD NEW WIND BRACE ON INSIDE-CHECK AT INTERMEDIATES |
|
10/04/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PRINT WITH D1 PAGE (GARAGE DETAIL 8/SD1 REQUIRED FROM SHEET 6) 2. CLIP DBL STUDS UNDER GIRDER 3. REPLACE DAMAGED 2ND FLOOR WIND BRACE (WEST END) 4. PROVIDE ANCHOR BOLTS IN INTERIOR SHEER WALLS PER PLAN. 5. INCOMPLETE NAILING @ INTERIOR SHEER 6. CLIP STAIR STRINGERS TO LANDING PER 3/D7 7. BLOCK SHEATHING ON GARAGE THAT IS RUN WRONG DIRECTION. 8. PROVIDE POSITIVE CONNECTION TO BACK PORCH LEDGER. |